Important
NOTE 2
The standards for minimum room volume are as follows.
1) No partition (shaded portion)
2) When there is an effective opening with the
adjacent room for ventilation of leaking refrigerant
gas (opening without a door, or an opening 0.15%
or larger than the respective floor spaces at the
top or bottom of the door).
3) If an indoor unit is installed in each partitioned
room and the refrigerant piping is interconnected,
the smallest room of course becomes the
object. But when a mechanical ventilation is
installed interlocked with a gas leakage detector
in the smallest room where the density limit is
exceeded, the volume of the next smallest room
becomes the object.
177-EN
IM_1141001201-2_Book.indd 89
IM_1141001201-2_Book.indd 89
Outdoor unit
Refrigerant piping
Indoor unit
Refrigerant piping Outdoor unit
Indoor unit
Very small room
Small
Medium
Large room
room
room
Mechanical ventilation device - Gas leak detector