Systemintegration
56
9.2.1
Blockmodell
Das Blockmodell zeigt, welche Ein- und Ausgangsdaten das Messgerät für den zyklischen
Datenaustausch zur Verfügung stellt. Der zyklische Datenaustausch erfolgt mit einem
FOUNDATION Fieldbus Master (Klasse 1), z.B. einem Leitsystem etc.
Anzeigetext (xxxx... = Seriennummer)
RESOURCE_ xxxxxxxxxxx
SETUP_ xxxxxxxxxxx
ADVANCED_SETUP_ xxxxxxxxxxx
DISPLAY_ xxxxxxxxxxx
HISTOROM_ xxxxxxxxxxx
DIAGNOSTIC_ xxxxxxxxxxx
EXPERT_CONFIG_xxxxxxxxxxx
EXPERT_INFO_xxxxxxxxxxx
SERVICE_SENSOR_xxxxxxxxxxx
SERVICE_INFO_xxxxxxxxxxx
TOTAL_INVENTORY_COUN-
TER_xxxxxxxxxxx
HEARTBEAT_RESULTS1_ xxxxxxxxxxx
HEARTBEAT_RESULTS2_ xxxxxxxxxxx
HEARTBEAT_RESULTS3_ xxxxxxxxxxx
HEARTBEAT_RESULTS4_ xxxxxxxxxxx
HEARTBEAT_TECHNOLOGY_ xxxxxxxxxxx
ANALOG_INPUT_1_xxxxxxxxxxx
ANALOG_INPUT_2_xxxxxxxxxxx
ANALOG_INPUT_3_xxxxxxxxxxx
ANALOG_INPUT_4_xxxxxxxxxxx
DIGITAL_INPUT_1_ xxxxxxxxxxx
DIGITAL_INPUT_2_ xxxxxxxxxxx
MULTI_DIGITAL_OUTPUT_ xxxxxxxxxxx
PID_ xxxxxxxxxxx
INTEGRATOR_xxxxxxxxxxx
9.2.2
Zuordnung der Messwerte in den Funktionsblöcken
Die Eingangswert eines Funktionsblocks wird über den Parameter CHANNEL festgelegt.
Modul AI (Analog Input)
Beschreibung
Es stehen vier Analog Input Blöcke zur Verfügung
CHANNEL
Messgröße
0
Uninitialized (Werkeinstellung)
7
Temperatur
9
Volumenfluss
11
Massefluss
Proline Promag P 200 FOUNDATION Fieldbus
Basisindex
Beschreibung
400
Resource block
600
Tranducer block "Setup"
800
Tranducer block "Advanced setup"
1000
Tranducer block "Display"
1200
Tranducer block "HistoROM"
1400
Tranducer block "Diagnostic"
1600
Tranducer block "Expert configuration"
1800
Tranducer block "Expert information"
2000
Tranducer block "Service sensor"
2200
Tranducer block "Service info"
2400
Tranducer block "Totalizer"
2600
Tranducer block "Hearbeat results 1"
2800
Tranducer block "Heartbeat results 2"
3000
Tranducer block "Heartbeat results 3"
3200
Tranducer block "Heartbeat results 4"
3400
Tranducer block "Heartbeat"
3600
Analog Input Funktionsblock 1 (AI)
3800
Analog Input Funktionsblock 2 (AI)
4000
Analog Input Funktionsblock 3 (AI)
4200
Analog Input Funktionsblock 4 (AI)
4400
Digital Input Funktionsblock 1 (DI)
4600
Digital Input Funktionsblock 2 (DI)
4800
Multiple Digital Output block (MDO)
5000
PID Funktionsblock (PID)
5200
Integrator Funktionsblock (INTG)
Endress+Hauser