Addition of refrigerant

After vacuuming work, exchange the vacuum pump with the refrigerant bomb and then start the additional charging
work of refrigerant.
Calculation of additional refrigerant charge amount
Refrigerant charge amount at shipment from the factory does not include the refrigerant for pipe at the local site.
For refrigerant to be charged in pipe at the local site, calculate the amount and charge it additionally.
NOTE) If the additional refrigerant amount indicates minus as the result of calculation, use the air conditioner
without addition of refrigerant.
Outdoor unit Model
Heat pump
model
Charging amount (kg)
Outdoor unit Model
Cooling only
model
Charging amount (kg)
Additional refrigerant
charge amount at local site
Table 1
Liquid pipe dia. (mm)
Additional refrigerant amount/1m liquid pipe (kg/m)
Table 2
Combined HP
Combined outdoor units
(HP)
(HP)
5
5
6
6
8
8
10
10
12
12
14
8
6
16
8
8
18
10
8
20
10
10
12
10
22
8
8
12
12
24
8
8
26
10
8
Charging of refrigerant
• Keeping valve of the outdoor unit closed, be sure to charge the liquid refrigerant into service port at liquid side.
• If the specified amount of refrigerant cannot be charged, open fully valves of outdoor unit at liquid and gas sides,
operate the air conditioner in COOL mode under condition that valve at gas side is a little returned to close side
(MAP0801
, MA1001
, MAP1201
choke the refrigerant slightly by operating valve of the bomb to charge liquid refrigerant. The liquid refrigerant may
be charged suddenly, therefore be sure to charge refrigerant gradually.
• When refrigerant leaks and refrigerant shortage occurs in the system, recover the refrigerant in the system and
recharge refrigerant newly up to the correct level.
<Entry of refrigerant charge amount>
• Fill the additional refrigerant record column of the wiring diagram indication plate with the additional refrigerant
amount at installation work, total refrigerant amount and the name of the service man who charged refrigerant
at installation time.
• The total refrigerant amount means the total value of the refrigerant amount at shipment and the additional
refrigerant amount at installation time. The refrigerant amount at the shipment is one described on the "Unit
nameplate".
All manuals and user guides at all-guides.com
MMY-MAP0501HT∗ ∗ ∗ ∗ ∗ MMY-MAP0601HT∗ ∗ ∗ ∗ ∗ MMY-MAP0801HT∗ ∗ ∗ ∗ ∗ MMY-MAP1001HT∗ ∗ ∗ ∗ ∗ MMY-MAP1201HT∗ ∗ ∗ ∗ ∗
8.5
MMY-MAP0501T8 MMY-MAP0601T8 MMY-MAP0801T8 MMY-MAP1001T8 MMY-MAP1201T8
8.0
= Real length
× Additional refrigerant charge
of liquid pipe
amount per 1m liquid pipe (Table 1)
0.025
C (Corrective amount of refrigerant)
(kg)
0.0
0.0
1.5
2.5
3.5
0.0
0.0
0.0
3.0
5.0
6
0.0
7.0
8
–4.0
8
–4.0
only), and then charge refrigerant into service port at gas side. In this time,
REQUIREMENT
+ Corrective amount of refrigerant
6.4
9.5
12.7
0.055
0.105
Combined HP
Combined outdoor units
(HP)
(HP)
28
10
10
30
10
10
12
10
32
8
8
12
12
34
10
8
12
12
36
10
10
38
10
10
40
10
10
42
12
10
44
12
12
46
12
12
48
12
12
18
12.5
11.0
combined horse power (Table 2)
15.9
19.1
0.160
0.250
0.350
C (Corrective amount of refrigerant)
(kg)
8
–2.0
10
0.0
10
1.0
8
8
–6.0
10
3.0
8
8
–6.0
12
4.0
8
8
–6.0
10
8
–6.0
10
10
–5.0
10
10
–4.0
10
10
–2.0
12
10
0.0
12
12
2.0
22.2