The minimum section must be 4 dm
than 200 mm, or 6.25 dm
The draught created by the flue must be sufficient, but not excessive.
A too big flue section can feature a too big volume to be heated and consequently cause difficulties in the operation of
the appliance; to avoid this, tube the flue along its whole height. A too small section causes a decrease of the draught.
The flue and the metallic pipe of connection must be properly spaced from any flammable materials or fuels
through a proper insulation or an air cavity.
It is forbidden to let plant piping or air feeding channels pass in the same flue. Moreover, it is forbidden to create
movable or fixed openings on the same for the connection of further other appliances.
5.1. CHIMNEY CAP
The draught of the flue depends also on the suitability of the chimney cap.
Therefore, if it is handicraft constructed, the output section must be more than twice as big as the internal section of
the flue. Should it be necessary to exceed the ridge of the roof, the chimney cap must assure the discharge also in
case of windy weather (Picture 8).
The chimney cap must meet the following requirements:
•
have internal section equivalent to that of the stack.
•
have a useful output section twice as big as the flue internal one.
•
be manufactured in such a way as to prevent the penetration of rain, snow, and any other foreign body in the
flue.
•
be easily checkable, for any possible maintenance and cleaning operation.
(1) Industrial chimney cap
with pre-fabricated
elements – it allows an
excellent discharge of the
smokes.
2 m
1
m
50 cm
20
2
(for example 20 x 20 cm) for appliances whose duct diameter is lower
2
(for example 25 x 25 cm) for appliances with diameter greater than 200 mm.
10 m
(1) The chimney cap must not show hindrances within 10 m from
walls, pitches and trees. Otherwise raise it of at least 1 m over the
hindrance.
The chimney cap must exceed the ridge of the roof of at least 1 m.
>A
H min.
α
INSERTO Crystal 50 – 50v – 50v p30 – 70 – 80 – 100
(2) Handicraft chimney
cap. The right output
section must be at least
twice as big as the internal
section of the flue (ideal
value: 2.5 times).
(1) In case of flues side by side, a chimney cap must be higher
than the other one of at least 50 cm in order to avoid pressure
transfers between the flues themselves.
> _ A
0,5 m
(1)Ridge axis
(2)Roof
(3) Chimney cap for
steel flue with internal
cone deflector of
smokes.
Picture 8
Picture 9
Picture 10
Picture 11
6096801 - Rev.17 – EN