ENG
3.7.2
Electrical data
Designation
Rated voltage * ***
Rated frequency *
Functional area
Power consumption * A35 / A35
Condensate evaporator power consumption
Nominal current *
Start-up current *
*
Data on the type plate.
***
Adapt the upstream fuse if the rated voltage changes, see "Adapting the unit to the mains voltage", Page 46.
3.7.3
Dimensions
Designation
Height
Width
Depth with cover (standard)
Weight
Installation attitude
Unit construction
3.7.4
Other unit data
Designation
Anti-corrosion protection
Protection category
Operating Manual | Roof-mounted Cooling Unit | Standard Controller (SC) – 400 / 460 V, 3~ | 086100040b
P
50 Hz
el
P
60 Hz
el
P
el
I
50 Hz
nom max
I
60 Hz
nom max
I
50 Hz
Start max
I
60 Hz
Start max
Standard: Galvanized, electrostatically powder-coated
(200°C)
Variant: Stainless-steel hood
When used as intended:
•
IP 54 relative to the switch cabinet (EN 60529).
•
IP 34 relative to the environment (EN 60529).
Model DTT 6801
400 / 460 V, 3~
50/60 Hz
DIN IEC 60038
1601 W
1989 W
30 to 110 W (A35/A35 approx. 70 W)
4.6 A
4.5 A
17.1 A
19.5 A
Model DTT 6801
485 mm
795 mm
575 mm
77 kg
Vertical
Standard: Steel sheet/plastic
25/26