Maintenance

8.
Maintenance
WARNING Electrocution
Disconnect the appliance from the power supply before
carrying out work inside the appliance.
Activity

Cleaning the heat exchanger and condensate pan

Condensate drain
Air ducts
8.1
Cleaning the heat exchanger and condensate
pan
f Open the appliance cover. See chapter "Opening the appli-
f
ance cover" in the operating instructions.
VRL-C 300:
6
4
5
1 Heat exchanger
2 Reheating coil (not installed in some appliances)
3 Fixing screws for heat exchanger retainer
4 Condensate pan fixing screws
5 Condensate pan
6 Condensate pan fixing screws
7 Mounting bracket for heat exchanger
VRL-C 6 25, VRL-C 870:
6
5
4
1 Heat exchanger
2 Reheating coil (not installed in some appliances)
3 Fixing screws for heat exchanger retainer
4 Condensate pan fixing screws
5 Condensate pan
6 Mounting bracket for heat exchanger
f Undo the fixing screws for the heat exchanger retainer.
f
f Pull the heat exchanger retainer down and out.
f
f Undo the fixing screws of the condensate pan.
f
www.stiebel-eltron.com
Maintenance inter-
val (in years)
1
7
3
2
1
6
2
3
Material losses
!
f Remove the condensate pan from the appliance
f
carefully as it may still contain water.
f VRL-C 300: Undo the fixing screws at the end of the conden-
f
sate pan.
f VRL-C 6 25, VRL-C 870: The condensate pan is pushed hori-
f
zontally on to a bolt on the exhaust air fan side. Carefully pull
the condensate pan towards the heat exchanger.
1
f Carefully tilt the condensate pan down and pull the conden-
f
1
sate pan towards the heat exchanger.
3
f Remove the condensate pump float from its retainer in the
f
condensate pan.
f Remove the condensate pan from the appliance.
f
f Carefully clean the condensate pan with lukewarm water.
f
CAUTION Injury
!
The heat exchanger weighs approx. 20 kg.
f During removal, take the weight of the heat ex-
f
changer into consideration.
f Use suitable load-handling equipment.
f
Material losses
!
When removing and cleaning the heat exchanger, take
care not to damage the heat exchanger fins.
f Undo the fixing screws for the reheating coil.
f
Material losses
!
Never expose the reheating coil wiring to any tensile load.
f Never allow the reheating coil to hang by the wiring.
f
f VRL-C 300: Undo the screws on the heat exchanger mounting
f
brackets.
f VRL-C 6 25, VRL-C 870: Undo the screws on the heat exchang-
f
er mounting bracket.
f To install the heat exchanger with the same orientation at a
f
later time, mark the installation position of the heat exchang-
er before removing it.
f Carefully remove the heat exchanger from the unit. Do not let
f
it fall.
f Use a commercially available vacuum cleaner to remove dust
f
and other loose dirt particles from the intake and discharge
surfaces.
f If required, clean the heat exchanger with warm water
f
(max. 55 °C) and a commercially available detergent. Do not
use solvents.
f Flush the heat exchanger with water.
f
f Allow the heat exchanger to dry completely.
f
VRL-C 300/625/870 |
29