DPX
pour exemple :
TM
1250
xxxxxxx
xxxxxxxx
MCCBs from 500 to 1250 A
0258 04
Dimensions (p. 97)
Technical data (p. 81-82)
Confirm to IEC 60947-2
Fixed version - Front terminals
Max. rated voltage 690 V A - 50/60 Hz
Thermal release adjustable from 0.8 to 1 In
Magnetic release adjustable from
5 to 10 < 1 000 A ≤ 3 to 6 In
Integrated label holder
DPX 1250
Pack
Cat. nos.
Breaking capacity Icu : 50 kA (400 V A)
3 P
4 P
(1)
In
1
0258 00 0258 07 500
1
0258 01 0258 08 630 A
1
0258 02 0258 09 800 A
1
0258 03 0258 10 1000 A
1
0258 04 0258 11 1250 A
DPX-H 1250
Breaking capacity Icu : 70 kA (400 V
3 P
4 P
(1)
In
1
0258 14 0258 21 500 A
1
0258 15 0258 22 630 A
1
0258 16 0258 23 800 A
0258 17 0258 24 1000 A
1
1
0258 18 0258 25 1250 A
DPX-L 1250
Breaking capacity Icu : 100 kA (400 V
3 P
4 P
(1)
In
0258 28 0258 37 500 A
1
1
0258 29 0258 38 630 A
1
0258 31 0 258 40 1000 A
1
0258 32 0258 41 1250 A
(1)
necessary auxiliaries
68
Bold packing quantity is our mandatory packing. Orders to be placed by Legrand (India) stockists in multiples of the same.
For automatic version add 2 motor operators and
Bold catalogue numbers are products normally available with Legrand (India) stockists.
Cat. nos. that are not bold delivery within 4 - 8 weeks from the date of order.
DPX
pour exemple :
TM
1250
xxxxxxxx
rotary handles and
other accessories
0262 61
0262 60
Confirm to IEC 60947-2
Fixed version - Front terminals
Max. rated voltage 690 V A - 50/60 Hz
Thermal release adjustable from 0.8 to 1 In
Magnetic release adjustable from 5 to 10 < 1 000 A ≤ 3 to 6 In
Integrated label holder
Rotary handles
Pack
Cat. nos.
Available in two versions
The vary-depth handle includes the connecting rod,
the bracket, the self-adhesive drilling template, the
mounting accessories and the door locking
mechanism
1
0262 61 Direct on DPX
1
0262 83 Vary-depth handle
Locking accessories for rotary handle
1
OS0262 25/3 For locking the rotary handle (Direct type only)
(set of 3 locks with keys)
A
)
Phase barriers
Used to isolate the connections between each pole
1
0262 66 Set of 3 insulation shields
Padlock support
For locking the handle in "OFF" position
1
0262 60 For handle
A
)
Motor
For remote making and breaking of a DPX MCCB
and reset in the event of tripping on a fault
A lock prevents operation when working on the line.
1
0261 23 Front operated 230 V
Supply inverter type
Mounting plate
1
0264 10 For mechanical interlock of 2 DPX MCCBs
Electronic control box
For detecting the absence of voltage or a drop in
voltage : triggers the opening of a power supply
source
1
0261 93 Standard
xxxxxxx
OS0262 25/3
A
=
/
0262 66