Adjust 100 % application range setting
General applications
Demanding
applications
Interface detection
CLS200 Digital
1.
2.
CLS300 Digital
1.
2.

Switch Point adjustment

CLS200 Digital
1.
2.
3.
Note:
Off switch point) of 10% must be maintained for reliable operation. In some situations it may
be desirable to increase the hysteresis between the two switch points to prevent false
tripping (e.g. turbulence in the process).
CLS300 Digital
1.
2.
3.
Page EN-14
Downloaded from
www.Manualslib.com
Application
dry solids
low viscosity liquids
hygroscopic / wet solids
high viscosity and high
conductivity liquids
liquid A / liquid B
foam / liquid
Open the menu View – Display and select the tab Transducer Block: Discrete Input
(Part 1). Make a note of the Sensor Value (digits) when the device is in the setup
condition that most closely represents the process (refer to table above).
Add 1000 counts to the Sensor Value noted in step 1and enter this new value in the
parameter view field: > Input > Transducer Block: Discrete Input > Range of Application >
100%.
Open the menu View – Display and select the tab Transducer Block: Discrete Input
(Part 1). Make a note of the Sensor Value (digits) when the device is in the setup
condition that most closely represents the process (refer to table above).
Enter the sensor value in the parameter view field: > Input > Transducer Block: Discrete
Input > Range of Application > 100%.
Define the application range (from tables above).
Open the menu View–Display, and select the tab Transducer Block: Discrete Input
(Part 1), to view the actual Sensor Value, the Sensor Value Discrete, the actual valid
Switch Point and Hysteresis
Go to Input > Transducer Block: Discrete Input > Switch behavior.
- Edit the value of Switch Point 1 (default 55%).
- Edit the value of Switch Point 2 (default 45%) to adjust the Hysteresis.
A minimum hysteresis (difference between the Off to On switch point and the On to
Define the application range (from tables above).
Open the menu View–Display, and select the tab Transducer Block: Discrete Input
(Part 1), to view the actual Sensor Value, the Sensor Value Discrete, the actual valid
Switch Point and Hysteresis
Go to Input > Transducer Block: Discrete Input > Switch behavior.
- Edit the value of Switch Point 1 (default 55%).
- Edit the value of Switch Point 2 (default 45%) to adjust the Hysteresis.
Pointek CLS200/300 (Digital) – QUICK START MANUAL
manuals search engine
Material
Sensor fully covered
Sensor fully covered
Immerse the sensor in the material that
has the highest dielectric constant.
Setup conditions
7ML19985XA82