Wiring instructions
- Use a 24Vdc ballast to power the Master LMS QUICK keypad
Da Da - +
- Connect the Split&Play to the master keypad (pay attention to polarity + and -)
NOTE: if polarity is incorrect, the DALI bus switches off and does not work (nothing actually
breaks down though)
Max distance: 300m
Da Da - +
- Wire the lamps to the outputs of groups A, B, C and D of the Split&Play
Connect max 3 RGB/RGBW groups
GROUP D can only be monochromatic
RGB LED, RGB fluorescent and RGBW fluorescent lamps must belong to separate
groups
follow the rule on the control of overall loads
In the case of the Split&Play, only iGuzzini RGB/RGBW lamps can be
controlled
- Connect the peripherals freely.
- Check the overall number of loads. RULE ON LOAD CONTROL: MAX 80 OVERALL LOADS
- RGB/RGBW groups cannot be dimmed
Key combinations
INSTALLATION
To start installation through the Split%&Play, press the following key combination:
CHECKS
- TEST ON PROPER MULTISENSOR INSTALLATION
- After a few seconds, the Group A key switches
on and flashes. This means the lamp-search
procedure has begun.
- Lamps belonging to Group A are switched off,
while any lamp that gets detected will flash
- The lamps belonging to the other groups stay
off
- Once Group A has been completed, all its
lamps reach maximum level and Group B search
begins. Group A key LED stays on and Group B
LED switches on the keypad.
- Go on until the 4 groups have been completed
- Once the installation has been completed, if all
the groups have lamps, the 4 LEDs of group keys
will be on. If some groups are missing, only the
LEDs with the groups having lamps will stay on.
- Press the following key combination.
- Description: all properly-installed light sensors
will flash the green and red LEDs for app. 5
seconds.
- PRESENCE-SENSOR OPERATION TEST
DISABLING BEEP FROM KEYPAD: hold down the following keys. Do as above to restart the
beep sound.
SHORT-CIRCUIT REPORTING
All lamps working at 100%. The LED of On/Off key is flashing.
Master keypad is short-circuit protected.
6
Description: the system uses this key
combination to simulate a switch-off from HD (30
seconds until minimum value, then OFF). Operate
one specific sensor to make sure it switches on
again and is properly working.