4.4.2 Connection of the frequency output
The frequency output may be connected to a programming logic controller (PLC) or a
counter.
Connection to a PLC is done on the basis of the following diagrams:
V+
1 2 3 4 5 6
4...20 V+ V- PE Pls+Pls-
8041
Connection to a PLC
with common - (PNP)
Connection of a load is done on the basis of the following diagrams:
V+ 0V
1 2 3 4 5 6
4...20 V+ V- PE Pls+Pls-
8041
Connection to an electro-
mechanical counter or relay
INSTALLATION
INPUT
0V
I
I
28
V+
1 2 3 4 5 6
4...20 V+ V- PE Pls+Pls-
8041
Connection to a PLC
with common + (NPN)
V1
GND1
1 2 3 4 5 6
4...20 V+ V- PE Pls+Pls-
8041
Connection to an electronic
counter with powered input
0V
INPUT
I
V2
GND2
I
8041