en
Operating instructions PA 10/ 20 PA X 10-10/..-15 / PA X 20-10/ ..-15
7.1
Changing the tones by external control
It is possible to obtain up to three additional tone types using the following electrical controls for applications
that require additional tones in addition to the base tone.
The desired base tone (♪, see tone type table in the Annex) is always set first with the tone selector switch S3
on the driver board. The corresponding additional tones (C1, C2, C1+C2) can be found in the "Control of
tones" table in the Annex.
7.1.1
Stage selection via control input (TAS), AC and DC versions
Note:
Always apply the supply voltage together with the control inputs.
Caution: If the control voltage is higher than the supply voltage or the supply voltage is not present at all, the
operating current will be supplied via the control inputs. A corresponding carrying capacity has to then be en-
sured.
Negative control: (Factory setting)
Switch setting should be as follows:
➢ Switch S2: with reverse polarity protection, (with rectifier)
➢ Switch S1: to „–"
Operating voltage
Positive control:
Switch setting should be as follows:
➢ Switch S2: with reverse polarity protection,
(with rectifier)
➢ Switch S1: to „
" (positive control)
+
Operating voltage
03/2020
DC version:
(on the driver board)
Tone C1
Tone C2
S2
(On the driver board)
Tone C1
Tone C2
Page 10 / 13
S2
S1
S1
086200001