9.2.5 Power input and power consumption
Tolerance: ± 10 %
This display shows the actual pump input power from the mains
supply. The power is displayed in W or kW.
The pump power consumption can also be read from this display.
The value of power consumption is an accumulated value
calculated from the pump's birth and it cannot be reset.
9.2.6 Operating hours
Tolerance: ± 2 %
The value of operating hours is an accumulated value and cannot
be reset.
9.2.7 Lubrication status of motor bearings (only 11-22 kW)
This display shows how many times the motor bearings have
been relubricated and when to replace the motor bearings.
When the motor bearings have been relubricated, confirm this
action in the INSTALLATION menu.
See section
9.3.14 Confirming relubrication/replacement of motor
bearings (only three-phase
pumps). When relubrication is
confirmed, the figure in the above display will be increased by
one.
9.2.8 Time till relubrication of motor bearings (only 11-22 kW)
This display shows when to relubricate the motor bearings.
The controller monitors the operating pattern of the pump and
calculates the period between bearing relubrications. If the
operating pattern changes, the calculated time till relubrication
may change as well.
The displayable values are these:
•
in 2 years
•
in 1 year
•
in 6 months
•
in 3 months
•
in 1 month
•
in 1 week
•
Now!
18
9.2.9 Time till replacement of motor bearings
(only three-phase pumps)
When the motor bearings have been relubricated a prescribed
number of times stored in the controller, the display in section
9.2.8 Time till relubrication of motor bearings (only 11-22 kW)
be replaced by the display below.
This display shows when to replace the motor bearings.
The controller monitors the operating pattern of the pump and
calculates the period between bearing replacements.
The displayable values are these:
•
in 2 years
•
in 1 year
•
in 6 months
•
in 3 months
•
in 1 month
•
in 1 week
•
Now!
9.3 Menu INSTALLATION
9.3.1 Control mode
Without sensor
(uncontrolled)
Select one of the following
control modes (see fig. 16):
•
Controlled
•
Uncontrolled.
If the pump is connected to a bus, the control mode
Note
cannot be selected via the R100. See section
14. Bus
signal.
9.3.2 Controller
E-pumps have a factory default setting of gain (K
time (T
). However, if the factory setting is not the optimum
i
setting, the gain and the integral time can be changed in the
display below.
•
The gain (K
) can be set within the range from 0.1 to 20.
p
•
The integral time (T
) can be set within the range from 0.1 to
i
3600 s. If 3600 s is selected, the controller will function as a
P controller.
•
Furthermore, it is possible to set the controller to inverse
control, meaning that if the setpoint is increased, the speed
will be reduced. In the case of inverse control, the gain (K
must be set within the range from -0.1 to -20.
will
With pressure sensor
(controlled)
Select one of the following
control modes (see fig. 16):
•
Controlled
•
Uncontrolled.
) and integral