Verfügbare Sprachen

Continuous
Model
output
MI­/TMI­
2000 W
2500 W
3000 W
* One set contains one positive and one negative wire .
** Recommended capacity of the batteries during permanent power .
*** Actual combination of fuses may differ .
ѥ
Warning!
Fire hazard!
If 2 sets of battery cables included the scope of delivery, the two of them have to be
installed . Failure to comply the instructions can easily cause an overheating of the over-
loaded cables and even dangerous cable fires .
Caution!
Please note the capacity!
An underrun of the recommended battery capacity can cause a loss of performance or
serious use restrictions as a result of voltage drops .
Caution!
Please respect a sufficient ventilation!
The inverter produces heat loss . The device is equipped with a thermal overload pro-
tection . An insufficient ventilation can affect the function of the inverter, because the
inverter can shut itself down for safety reasons .
28
[
ECTIVE
®
POWER INVERTER – MI-/TMI-SERIES
Input
Battery cabel*
voltage
202
12 V
16 mm², 2 sets
204
24 V
10 mm², 2 sets
208
48 V
252
12 V
16 mm², 2 sets
254
24 V
10 mm², 2 sets
258
48 V
302
12 V
16 mm², 2 sets
304
24 V
10 mm², 2 sets
308
48 V
Fuse/
Unit***
35 A × 8
20 A × 8
6 mm², 2 sets
10 A × 8
35 A × 10
20 A × 10
6 mm², 2 sets
10 A × 10
35 A × 12
20 A × 12
6 mm², 2 sets
10 A × 12
]
Battery
capacity**
≥320 Ah
≥160 Ah
≥80 Ah
≥400 Ah
≥200 Ah
≥100 Ah
≥480 Ah
≥240 Ah
≥120 Ah