CAUTION! THE AUTOSET PROCEDURE DESCRIBED BELOW IS MANDATORY!
During the AUTOSET phase, the control unit performs a number of opening and closing movements during which essential operating
parameters are set, including:
- Start- and end-of-run positions.
- Start of the slowdown phases.
- Torque values applied during panel movement.
- Recognition of the device connected to the PHOT input.
Procedure:
1) With the control unit connected to the mains, press and hold down the PU1 + PU2 keys until the 3 red LEDs light up cyclically.
2) The AUTOSET procedure starts, some opening and closing movements are commanded.
3) At the end of the procedure the panel stops in the open position and the LED lights remain steady for 5s to confirm AUTOSET
correctly carried out.
During the AUTOSET phase, a deceleration space different from the default space set by the control unit, can be set. Proceed as follows:
1) Start-up an AUTOSET procedure.
2) The panel will start slowly opening and closing.
3) A CLOSING movement will then start at normal speed, during which the slowdown starting point can be selected using an S.S.
command (transmitter, S.S. input, PU1) keys when needed.
4) An OPENING movement will then start at normal speed, during which the slowdown starting point can be selected using an S.S.
command (transmitter, S.S. input, PU1) keys when needed.
TCA Trimmer
Allows to adjust automatic closing time. Adjustment may vary from a minimum of 3s to a maximum of 180s.
With the TCA trimmer turned completely clockwise the TCA is disabled.
With TCA active and the panel open, the LD1 LED starts flashing quickly to indicate the counting of the TCA time in progress.
AMP Trimmer
Adjustment of the sensitivity of the amperometric sensor for obstacle detection during opening and closing.
Rotate the trimmer clockwise (+) to increase the torque, turn counter-clockwise (-) to decrease the torque.
In the case of obstacle detection:
- Stops movement during opening.
- Stops and reopens the panel for about 3s during closing .
CAUTION:
The AMP trimmer increases or decreases the value that the control unit has set in the various points of the run during AUTOSET phase.
It should therefore be set only after a complete AUTOSET procedure and in compliance with the regulations in force.
DIP 1
DIP 1 enables to:
- Enable/disable pre-flashing
- Enable/disable SASO function (panel stop before mechanical opening stop).
- Enable/disable remote transmitter acquisition
The procedure involves switching DIP1 to ON, carrying out the operations described, then switching it back to OFF to confirm
programming.
PRE-FLASHING enabling/disabling
Switching DIP1 to On with the PU2 key will enable or disable pre-flashing.
The LD1 LED indicates the status of the function:
LED LD1 on = Pre-flashing enabled. The flashing light activates 3s before the motor starts.
LED LD1 off = Pre-flashing disabled. (default)
CAUTION: Switch DIP 1 to OFF at the end of programming.
Enable/disable SASO function
Switching DIP1 to On with the PU1 key enables or disables the SASO function.
The SASO function involves stopping the panel before the mechanical opening stop (about 1 cm), thus obtaining a gradual stop without
vibrations.
The LD2 LED indicates the status of the function:
LED LD2 on = SASO enabled (default)
LED LD2 off = SASO disabled
CAUTION: Switch DIP 1 to OFF at the end of programming.
Enabling/disabling of remote transmitter acquisition
Switching DIP1 to On by simultaneously pressing PU1 + PU2 enables or disables remote acquisition, as described in the paragraph
"Remote acquisition of transmitters".
Please note: Reception of duplicate "AK" series transmitters is simultaneously enabled or disabled.
The LD3 LED indicates the status of the function:
LD3 LED on = Remote acquisition enabled (default)
LD3 LED off = Remote acquisition disabled
CAUTION: Switch DIP 1 to OFF at the end of programming.
AUTOSET
CHANGES TO SLOWDOWN SPACES
TRIMMER FUNCTION
DIP-SWITCH FUNCTION (S1)