Maintenance

Do not use corrosive liquids to clean the device.
EN
The devices are maintenance-free. However, to ensure that the entire alarm system functions
correctly, check the function and all the sensors. For the maintenance intervals, please refer to
the manual of the NVO5-11 warning device and the operating instructions for the sensors.
1.6

Delivery, Transport and Storage

Check the packaging and contents for damage. In the event of damage, notify the postal
service or express agent and inform the supplier.
Check the scope of supply for completeness and correctness using the order and delivery
papers.
Keep the original packaging.
The device should always be stored or transported in the original packaging.
Always store the device in a dry and clean environment. Observe the permissible storage
temperature (see data sheet).
1.7

Installation and Commissioning

1.7.1

Installation of the device

The device must not be mounted in a Zone 0 hazardous area according to Directive 94/9/EC
(ATEX). The device must not be installed in locations where aggressive media may occur.
The device must be de-energized during installation and maintenance. The supply voltage may
be connected only after the device has been fully installed and connected.
The attached identification plate is an integral part of the product and must not be removed.
The device is designed to degree of protection IP20.
When installing the device, do not exceed the permissible ambient temperature in the range of
-20 °C ... 60 °C (253 K ... 333 K).
1.7.2

Installation in connection with intrinsically safe circuits

Installation of the intrinsically safe power circuits of the devices is permitted in potentially
explosive zones, whereby, in particular, safe separation from all non-intrinsically safe power
circuits must be guaranteed.
The intrinsically safe current circuits must be installed according to valid setup regulations.
For the interconnection of the intrinsically safe field devices and the intrinsically safe power
circuits of the associated devices, the respective maximum values of the field device and the
associated device with regard to explosion protection must be observed (proof of intrinsic
safety). EN 60079-14/IEC 60079-14 must be observed.