Herunterladen Inhalt Inhalt Diese Seite drucken

Mechanical Data; As-Interface - Siemens 3RK1901-1GA00 Betriebsanleitung

Überspannungsschutzmodul
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 1
Technical data
Impulse test current
4
Overvoltage protection
Total current input
Rated discharge current I
Core - PU
Core - Core
Protection level U
at I
sp
sp
Core - PU
Core - Core
at 1 kV / µs
Core - PU
Core - Core
Response time
Core - PU
Core - Core
Own current requirements (from AS-Interface
system)

Mechanical data

Degree of protect. (with coupl. module)
Weight
Dimensions (H x W x D) [mm]
Temperature range
Rated temperature
Ambient temperature
Storage temperature
Impulse test current of waveform 8/20
120
100
80
60
40
20
0
0
5
Rated discharge current I
sn
The rated discharge current is the peak value of an impulse current of the form 8/20 microseconds
(see fig.) for which the overvoltage protection module is designed, in accordance with a specified
test program.
Protection level U
:
sp
The protection level of an overvoltage protection module is the maximum instantaneous value of
the voltage at the terminals, determined from individual tests.
The protection level characterizes the ability of an overvoltage protection module to limit overvolt-
ages to a residual level.
of waveform 8/20
sn
t
a
T
u
T
a
T
s
10
15
t in µs
:

AS-Interface

AUX POWER
<3 mA
<3 mA
10 kA
10 kA
0.5 kA
0.5 kA
≤1.8 kV
≤1.8 kV
≤100 V
≤70 V
≤700 V
≤600 V
≤50 V
≤40 V
<100 ns
<100 ns
<1 ns
<1 ns
≤3mA
≤3mA
IP 67
Approx. 120 g
80 x 45 x 25
25 °C
–25 °C to 85 °C
–40 °C to 85 °C
t (µs) / rated discharge current, %
0
0
8
100
20
50
20
3RK1701-2KB08-0AA2

Werbung

Inhaltsverzeichnis
loading