13. GAS VALVE
Gas valve key
Pi
Gas supply pressure tap
14. PARAMETER SETTINGS
To programme the parameters of the boiler electronic board, proceed as follows:
• Press
and
together and hold them down for 6 seconds until programme row "P01" appears on the display alternated
with the set value;
• Press
to scroll the list of parameters;
• Press
the value of the selected begins flashing, press
• Press
to confirm the value or press
Further information concerning the parameters listed in the following table are supplied together with the required acces-
sories.
DESCRIPTION OF PARAMETERS
P01
-------
Gas used
P02
00 = METHANE - 01 = LPG
Hydraulic system
00 = instantaneous appliance
P03
05 = appliance with external storage boiler
08 = heating only appliance
Programmable relay 1 setting
P04
(See SERVICE Instructions)
Programmable relay 2 setting
P05
(See SERVICE Instructions)
External probe input configuration
P06
(See SERVICE Instructions)
P07..P09
Manufacturer information
P10
Remote control installation method
P11..P12
Manufacturer information
P13
Max. heating output (0-100%)
P14
DHW max. output
P15
Min. heating output (0-100%)
Maximum CH setpoint (°C)
P16
00 = 85°C - 01 = 45°C
P17
Pump overrun time in heating mode (01-240 minutes)
Burner ignition delay in CH mode (00-10 minutes) - 00=10
P18
seconds
P19
Manufacturer information
P20
Pump overrun time in DHW mode (seconds)
Anti-legionellosis function
P21
00 = Disabled - 01 = Enabled
P22
Manufacturer information
P23
Maximum DHW setpoint temperature (ACS)
P24
Manufacturer information
P25
No water safety device
P26..P31
Manufacturer information
P32..P41
Diagnostics (See SERVICE Instructions)
to exit without saving.
(0-100%)
to change the value;
FACTORY SETTINGS
1.12
1.24
1.28
08
08
08
100
100
100
29
24
28
33
40
00
00
00
00
00
00
02
04
00
--
00
--
80
84
80
74
100
00
00
03
03
07
30
00
00
60
35
00
--
--
7108194.01 (1-11/11)