ASTRALPOOLHEAT SERIES · AIR/WATER SYSTEM
ECO Temp Diff
1.0ºC
EOM
* * *
Filter Control
ON/Off
Comfort Function
Enabled/Disabled
SPA Control
Enabled/Disabled
V.SPA Time
50 sec
Mode SPA+POOL
1h / 03h
Delay time
02 min
Sample Time
30 min
Defrost Mode
1 / 2 / 3
© ASTRALPOOL 2008. ALL RIGHTS RESERVED. CONFIDENTIAL AND PROPRIETARY DOCUMENT.
Extra differential temperature added to Differential Temp
parameter when ECO mode is active.
If ECO Temp Diff is set to zero then the user cannot use the
ECO mode.
This screen defines the grade of energy efficiency the unit
will work on, where *** is the lowest grade of efficiency and
***** is the highest.
This screen sets whether the unit has control over the
filtration system or not. If this screen is set to Disabled, the
unit will only be able to heat water when the filtration system
in on.
This screen enables or disables the possibility to select
Comfort as an operation mode. If this screen is set to
Disabled, the unit will only be allowed to work on Filtration
mode.
This screen enables or disables the possibility to select SPA
as an operation mode.
1) Disabled: the unit will work only on Pool mode.
2) User Control: The unit will be able to work on Pool
or/and Spa water, user selectable.
3) External Control: The unit will work on Pool or/and
Spa by means of external terminals, see 5.13.
This screen set the time the unit will stop water flow during a
Pool ↔ Spa change. This time reflects the time needed for
the 3 way valves to switch from Pool ↔ Spa. It is useful to
set a time slightly larger than required to assure that the
change is complete.
This screen sets the timing when the unit is set to heat Pool
and Spa. In this example, the unit will heat Spa for 1 hour
and then will change to heat Pool for 3 hours. If temperature
setting is achieved, unit will change immediately.
This screen represents the time lapse between when the
machine should activate and when it really does. This screen
only appears if "Comfort function" is activated.
Only appears if "Confort function" is activated. This screen
represents time lapse between water temperature readings.
For instance, when water temp is within set point, unit will
check every 30 min whether water has came out of set point.
Depending on the units characteristics 3 types of defrost can
be selected:
1) Fan stop: By air with fan off.
2) Air+Fan: By air with fan on.
3) Cycle inversion: by hot gas by reversing the frigorific
circuit. (only reversible machines)
ENGLISH