Commissioning and operation
Table 10:
Valve address assignment for 4x bus coupler
AS-i data bit
D1.0
D1.1
D1.2
D1.3
AS-i 8DI/8DO-AUX
AS-i 4DI/4DO-AUX
and AS-i 4DI/4DO
1
Sol. 14
Sol. 14
Sol. 12
Sol. 12
Max. 2 valves with 2 solenoids
each
Max. 4 valves with 1 solenoid each
7.1.2
The numbering of the M8 connectors on the bus couplers
corresponds to the bit number.
With bus couplers with 8 inputs, the inputs I0 to I3 can be read
on data bit D1.0 to D1.3 of the first participant and the inputs I4
to I7 on data bit D2.0 to D2.3 of the second participant.
With bus couplers with 4 inputs, the inputs I0 to I3 can be read
on the data bit D1.0 to D1.3.
Input status is displayed by LEDs.
LED (yellow) lit: input on HIGH (active).