• Hold luminaire approximately level and snug up bolts
5.5-6.8N-m (4-5 foot-pounds).
• If more upward tilt of front of luminaire is needed,
first loosen front two bolts slightly, lift luminaire and
re-snug the back two.
• If downward tilt is needed, reverse procedure by
loosening back two bolts first.
• Once proper level has been achieved, tighten each
bolt to 23.05-25.760 N-m (17-19 foot-pounds)
alternating front to back along diagonal of bracket as
shown in Figure 1.
FIGURE 1
Under no conditions should bolts be torqued to level greater than
27.17 N-m. (20 ft-lbs)
Risk of injury. LED light source achieves full intensity immediately
upon being powered on. Do not look directly at LED light source
while energized.
4
WIRING
• NOTE: Make all electrical connections in accordance
with the National Electrical Code and any applicable
local code requirements including grounding.
• NOTE: Verify that supply voltage is correct by
comparing it to nameplate.
WARNING
CAUTION
IEC Units:
• Terminals are readily accessible on terminal board
and will accept service leads ranging in size from AWG
No. 16 through No. 6.
• Service leads (See fixture labeling for supply wire
temperature rating) should extend through mounting
bracket approximately 180mm (7 inches).
• Attach service leads to terminal board as shown on
luminaire nameplate.
• See table below for screw torques (See Table 1).
• Dimming Control Connections (See Table 2).
• A wiring diagram is provided on a label in luminaire.
TABLE 1. Terminal Board Torque Table UL Units
Wire Range Copper
10 - 16 SOL, STR
8 - 6 SOL, STR
STR6 SOL, STR
TABLE 2. Dimming Control Connections
O VDC (-)
Gray Lead
Up to 10 VDC (+)
Violet Lead
IEC Units:
• Power supply cable and dimming control cable (if
necessary) must be provided by customer.
• Power supply cable (each conductor: phase, neutral
and ground) should be maximum of 12AWG (2.5mm
and minimum of 16 AWG (1.5mm
with an overall cable diameter within the range of
7-12mm.
• Dimming control cable (0 to 10 VDC) (each conductor:
positive and negative) should be 18 AWG (1.0mm
solid or stranded with an overall cable diameter within
the range of 5-10mm.
Terminal Board Connections:
Terminal Board Position
L1
G
N/L2
Aluminium
Torque
3.4N-m (30 in lbs)
5N-m (45 in lbs)
) solid or stranded
2
Supply Type
High Line
Ground
Low Line/Neutral
2
)
)
2