11. General information:
– The regulation behaviour (overshoots in case of unfavourable temperature conditions) can be adapted via the parameter mixing valve
interval (factory setting 4s) in the heating circuit settings.
The mixing valve control serves to adapt the actual supply temperature to the nominal supply temperature. For this purpose, the mixing
valve is opened up or closed down in cycles according to the temperature difference. The break is determined by the difference
between the actual and nominal value. The higher the difference, the shorter the breaks.
4 sec. (230 V)
Mixing
valve
OPEND/
CLOSED
Illustr 11: Mixing valve interval OPEN/CLOSED
– The speed of the collector circuit pump (Wilo TEC ST 15/7) is controlled via a PWM signal. The control cable is connected to the
terminal PWM1 and the PWM speed control is activated at works.
– The extension module "Regtronic EM-B" (Oventrop item no. 1152098) can be used for the extension of the controller "Regtronic RS-B" by 6
sensor inputs and 5 relay outputs.
4 sec. (230 V)
Break
Valves, controls + systems
4 sec. (230 V)
Break
Break