Display
I N I B I T I N P U T
N O
P R O G R A M M I N G M E N U
S E T P R E S S U R E
3
,
5
D I F . S T A R T .
0
,
6
b a r
T I M E R S T O P
5 s
V I E W M O D E
S t a n d a r d
S E R I A L C O N T R O L
S l a v e
D I R E C T I O N
C H :
1
P L I N E
P S E T
2
,
2 b a r
3
,
5 b a r
IN MASTER & SLAVE MODE.
In case of group assembly, press the
SLAVE device will begin to light up intermittently, indicating that communication between both the devices is working properly. If
this does not work, examine the connection (Fig.6a, 6b or 6c).
18
If the installation does not have a minimum level sensor press the button
If the installation has a level sensor, use the buttons
This screen indicates switching from the Configuration menu to the programming phase.
This will be the working pressure of the system. Use the keys
ATTENTION! The required pressure should be 1 bar below the maximum pressure of the pump.
NOTE: In the case of pressure group installation, this work at the required pressure is set on the
MASTER device. Therefore, configuration of the required pressure in the SLAVE device is superfluous.
The default value is 0 bar. This pressure is what the system will subtract from the required pressure, thus
resulting in the final pressure at which the system will activate the pump when there is a request in the hydraulic
network. Use the keys
to change the initial value. It is advisable to keep this value between 0.3 and
0.6 bar. Example:
- Required pressure PRIC: 2 bar.
- Start-up differential 0.6 bar
- Final start-up pressure: 2 - 0.6 = 1.4 bar.
The differential value must be greater the lower the volume of the expansion vessel is.
The default SLEEP TIMER is 5". This will be used by the device to stop once the water consumption throughout
the installation has ceased. Use the keys
There are 2 screen options to choose from:
-STANDARD: "P LAV" (actual pressure of installation) and "P RIC" (pressure of work required)
-SERVICE: "Hz" is displayed (frequency of the drive of the variator), "P RIC" (work pressure required), "P LAV"
(actual pressure of installation) and "FL" (state of flow sensor).
The default value is "SLAVE".
In the case of individual assembly confirm "SLAVE" by pressing the button
In the case of Group installation (MASTER-SLAVE), the device to be designated as SLAVE is
configured the same way. In the MASTER device change the "slave" option to "master" by pressing
the button
.
This displays the communication line.
Press the
ENTER button The system will be configured showing the type of view previously chosen. Press
the button
ON/OFF to leave the manual operation mode.
In the case of group assembly press
ON / OFF button in the MASTER device, the
Description
ENTER to validate NO.
to change NO to YOU.
to change the initial value (2 bar).
to change the initial value.
ENTER.
ON/OFF only on the MASTER device.
or
button
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ON/OFF
AUT LED of the