Code Nr.
Level
Variable Name
122
Inst.
MIN COOL W T°
123
Inst.
MAX COOL W T°
124
Inst.
MIN COOL W T°
125
Inst.
MAX COOL W T°
126
Inst.
AUX NUMBER
BACKUP
127
Inst.
ELECBOIL
128
Inst.
EH PRIORITY
129
Inst.
AUX T°O
130
Inst.
AUX HYST
131
Inst.
AUX DELAY
132
Inst.
OAT BOILER
133
Inst.
SHW CARREXT
134
Inst.
SHW MAX HP T°
SHW DELTA
135
Inst.
MED T°
SHW DELTA
136
Inst.
ALARM T°
ROOM DELTA
137
Inst.
MED T°
ROOM DELTA
138
Inst.
MIN T°
BOILER WAIT
139
Inst.
TIME
LEGIONELLA
140
Inst.
FREQ
LEGIONELLA
141
Inst.
START TIME
LEGIONELLA
142
Inst.
TEMP
LEGIONELLA
143
Inst.
DURATION
LEGIONELLA
144
Inst.
TIME OVER
22
Description
In Cool mode, minimum water T° going to terminal zone 1(Cool climatic curve
zone 1)
In Cool mode, maximum water T° going to terminal zone 1(Cool climatic curve
zone 1)
In Cool mode, minimum water T° going to terminal zone 2(Cool climatic curve
zone 2)
In Cool mode, maximum water T° going to terminal zone 2(Cool climatic curve
zone 2)
Number of backup heaters
0. No backup heaters
1. 1 back up heaters output (to be selected in case of boiler backup)
2. 2 back up heaters output (2
nd
backup heater output activated after the
st
1
backup heater output)
½ ƽ ÌÀ½ º¹»ÃÍÈ ½Æ½Ê¿Ñ ËÇÍÊ»½
1: Electrical heater
2: Gas boiler
ÀÁË »Ç¼½ ¼½ Æ½Ë ÌÀ½ ½Ä½»ÌÊÁ» À½¹Ì½Ê ÇÍÌÈÍÌ ÈÊÁÇÊÁÌÑ º½ÌϽ½Æ º¹»Ã ÍÈ À½¹Ì½ÊË
(space heating) and booster heater (domestic hot water). It is only active if
code 127=1
0. All the electric heaters output can be activated at the same time, if required
1. Maximum 2 electric heaters output can be activated; booster heater has
lowest priority
2. Maximum 1 electric heaters output can be activated; back-up heater output
1 has the highest priority (backup heater output 2 in never ON)
3. Maximum 2 electric heaters output can be activated; booster heater has
lowest priority (backup heater output 2 in never ON)
4. Maximum 1 electric heaters output can be activated; booster heater has the
highest priority (backup heater output 2 in never ON)
The outdoor T° must be below this value to allow the backup heaters to be ON
(unless there is a failure to stop the outdoor unit and acode 1.4=1)
If the difference between water setpoint and water temperature is higher than
this value, backup heaters are allowed to turn on
Time delay (minutes) before switching the backup heaters ON
If in Heat mode, the outdoor temperature is less than the value of this code, the
outdoor unit is turned OFF and the Boiler is used as heat source. Set to
minimum value if this function is not required.
Domestic Hot Water
Defines if Domestic hot water is managed by the system control or by an
external control.
1. Managed by system control
2. Managed by system control with soloar
3. Managed by external control
If domestic hot water tank is not installed set code to 3 and set code 106.0=0
If domestic hot water temperature is equal to or higher than this value,
domestic hot water priority is 0
If domestic hot water temperature is equal to code 134- code 135 - this code,
domestic hot water priority is 0.5
If domestic hot water temperature is equal to or lower to code 134- code 135 -
this code, domestic hot water priority is 1
In heat mode: If room temperature is Room Setpoint - this code, room proirity is
0.5
In cool mode: If room temperature is Room Setpoint - this code, room proirity is
0.5
In heat mode: If room temperature is Room Setpoint - code 137 - this code,
room proirity is 1
In cool mode: If room temperature is Room Setpoint + code 137 + this code,
room proirity is 1
Time delay after which the boiler will be activated if domestic hot water priority
does not decrease due to heat pump operation.
If 0 is selected, boiler does not return on to support the domestic hot water
production.
Define how often (days) the disinfection cycle starts.
If 0 is selected, Disinfection is not performed.
Start time of the Disinfection cycle (hours)
T° to be reached in the Disinfection cycle
Disinfection dwell time (minutes). T° has to be equal to or higher than code 142
for this time period.
If Disinfection cycle is ot completed within this time (hours), the antilegionalla
cycle is considered failed.
Value range
Default
Min
Max
4 °C
20 °C
12 °C
4 °C
20 °C
18 °C
4 °C
20 °C
6 °C
4 °C
20 °C
12 °C
0
2
0
YUNA II :2
1
2
Others: 1
0
4
0
-30 °C
+40 °C
+4 °C
0 °C
10 °C
3 °C
0
60
10
-30 °C
+40 °C
-5 °C
1
3
3
40 °C
80 °C
55 °C
1 °C
15 °C
5 °C
1 °C
15 °C
5 °C
0.5 °C
5 °C
1 °C
0.5 °C
5 °C
1 °C
0
180
15
0
7
0
0
24
3
60
90
75 °C
5
180
30
2
12
4