Material
Selects the appropriate echo processing algorithms for the material.
Options
Response Rate
Sets the reaction speed of the instrument to measurement changes in the target
range.
Options
Use a setting just faster than the maximum filling or emptying rate (whichever is
greater).
Units
Sensor measurement units.
Options
Low Calibration Point
flanged versions
sensor
reference
point
threaded versions
sensor
reference
point
Distance from Sensor Reference to Low Calibration Point: usually process empty
level.
Values
High Calibration Point
Distance from Sensor Reference to High Calibration Point: usually process full level.
Values
Page EN-20
SITRANS LR250 (FF) – QUICK START MANUAL
*
LIQUID
LIQUID LOW DK (low dielectric liquid – CLEF
enabled
)
Response
Rate
*
SLOW
MED
FAST
M, CM, MM, FT, IN
Default: M
space
level
Range: 0.00 to 20.00 m
Default: 20.00 m
Range: 0.00 to 20.00 m
Default: 0.00 m
Fill Rate per Minute/Empty Rate per Minute
0.1 m/min (0.32 ft/min)
1.0 m/min (3.28 ft/min)
10.0 m/min (32.8 ft/min)
distance
High Cal.
Pt.
(process
full level)
algorithm
sensor
reference
point
Low Cal. Pt.
(process
empty
level)
7ML19985XN82