Electrically isolated from the basic
•
device
Signal status 0
Signal status 1
Internal resistance
Static destruction limit
•
Connecting to circuits with the
•
following peak values
Effective internal capacitance
Effective internal inductance
Galvanic isolation
Test voltage
7.5.2
Position feedback module
Position feedback module
Direct current output for position
feedback
1 current output, terminals 61 and 62
Rated signal range
Dynamic range
Auxiliary voltage U
H
External load R
[kΩ]
B
Transmission error
Temperature influence
Resolution
Residual ripple
For connecting to circuits with the
following peak values
Effective internal capacitance
Effective internal inductance
Galvanic isolation
Test voltage
46
Without explosion
protection or suitable for
use in the SIPART PS2
Ex d
± 35 V
-
-
-
The three outputs, the BI2 input and the basic device are galvanically isolated from
Without explosion
protection or suitable for
use in the SIPART PS2
Ex d
6DR4004-8J
+12 ... +35 V
-
-
Safe galvanic isolation from alarm option and basic device
With Ex protection Ex "ia"
≤ 4.5 V or open
≥ 13 V
≥ 25 kΩ
-
U
= DC 25.2 V
i
C
= negligibly small
i
L
= negligibly small
i
each other.
DC 840 V, 1 s
With Ex protection Ex ia
(only in temperature class
T4)
6DR4004-6J
2-wire connection
4 ... 20 mA, short-circuit proof
3.6 ... 20.5 mA
+12 ... +30 V
≤ (U
[V] - 12 V)/I [mA]
H
≤ 0.3 %
≤ 0.1%/10 K (≤ 0.1%/18 °F)
≤ 0.1 %
≤ 1 %
U
= DC 30 V
i
I
= 100 mA
i
P
= 1 W
i
C
= 11 nF
i
L
= negligibly small
i
DC 840 V, 1 s
With Ex protection
Ex "ic", "nA", "t"
-
"ic":
U
= DC 25.2 V
i
"nA"/"t":
U
≤ DC 25.5 V
n
C
= negligibly small
i
L
= negligibly small
i
With Ex protection
Ex "ic", "nA", "t"
6DR4004-6J
+12 ... +30 V
"ic":
U
= DC 30 V
i
I
= 100 mA
i
"nA"/"t":
U
≤ DC 30 V
n
I
≤ 100 mA
n
P
≤ 1 W
n
C
= 11 nF
i
L
= negligibly small
i
SIPART PS2 (6DR5...)
A5E03436620-05, 09/2014