|
en
Safety-related information
1
Safety-related information
These instructions for use are available in further
languages and can be downloaded in electronic form via the
database for technical documentation (www.draeger.com/ifu)
or a printed version can be ordered free of charge via Dräger.
1.1
Safety statements
– Before using this product, carefully read these Instructions
for Use and those of the associated products.
– Strictly follow the instruction for use. The user must fully
understand and strictly observe the instructions. Use the
product only for the purposes and under the conditions
specified in this document.
– Comply with all local and national laws, rules, and
regulations associated with this product.
– Only trained and competent personnel are permitted to
inspect, repair and service the product as detailed in these
instructions for use. Further maintenance work that is not
detailed in these instructions for use must only be carried
out by Dräger or personnel qualified by Dräger.
– Dräger recommends a Dräger service contract for all
maintenance activities and that all repairs are carried out
by Dräger.
– Use only genuine Dräger spare parts and accessories.
Otherwise the proper functioning of the product may be
impaired.
– Do not dispose of the Instructions for Use. Ensure that
they are retained and appropriately used by the product
user.
– Only trained and competent users are permitted to use
this product.
– Maintenance must be performed as described, see
11 Maintenance.
– Only operate the product within the framework of a risk-
based alarm signaling concept.
– Before connecting this instrument to electrical devices not
mentioned in the IFU consult Dräger
– Notify Dräger in the event of any component fault or
failure.
– The instruments or components may not be modified in
any manner.
– The use of faulty or incomplete parts is forbidden.
– The appropriate regulations must be observed at all times
when carrying out repairs on these instruments or
components.
– Follow the directions of EN/IEC˽60079-29-2 for the
measurement of flammable gases.
®
Polytron
8100 EC-specific:
– WARNING: Risk of ignition of flammable or explosive
atmospheres! Substitution of components may impair
Intrinsic Safety.
8
1.2
Operating area and conditions
– For SIL applications observe the Dräger Polytron
Safety Manual.
– When exposed to a directed flow of air mixed with gas, the
measured values can be increased. See the
corresponding sensor data sheet for deviation values.
– Observe the specifications and restrictions in the
Instructions for Use and/ or data sheets for the sensors.
– CAUTION Risk of ignition of flammable or explosive
atmospheres! Not tested in oxygen enriched atmospheres
(>21% O
).
2
– Using the product in areas subject to explosion
hazards: Instruments or components for use in explosion-
hazard areas which have been tested and approved
according to national, European or international Explosion
Protection Regulations may only be used under the
conditions specified in the approval and with consideration
of the relevant legal regulations.
– Hazardous areas classified by zones: The device is
intended to be used only in hazardous areas classified
Zone 1 or Zone 2, within a temperature range as marked
on the device, where gases of explosion Groups IIA, IIB or
IIC and temperature class T4 or T6 (depending on the
maximum ambient temperature) or dusts of Groups IIIA,
IIIB or IIIC may be present.
– Hazardous areas classified by divisions: The device is
intended to be used only in hazardous areas Class I or II,
Div. 1 or Div. 2, within a temperature range as marked on
the device, where gases or dusts of Groups A, B, C, D or
E, F, G and temperature class T4 or T6 (depending on the
maximum ambient temperature) may be present.
1.3
Mechanical installation
– Strict compliance must be given to the local, state, national
codes and regulations that govern the installation of gas
monitoring equipment.
– The physical data of the gas or vapor to be detected and
the specifics of the application, (e.g. possible leaks, air
movement/draft, etc.) must be taken into account.
– The future use of accessories and maintenance
equipment must be kept in mind.
– The access of the gas or vapor to the sensor must not be
obstructed.
– The instrument must not be exposed to radiant heat that
will cause the temperature to rise beyond the limits stated
in 17.6 Environmental parameters. The use of a reflecting
shield is recommended.
– The instrument may be equipped with a dust plug at the
conduit entry. This plug is not explosion proof nor meant to
be watertight, and must be removed before connecting the
instrument to a sealed conduit or installation of a
flameproof cable gland.
– Unused openings must be closed with a plug. For correct
tightening torques of conduit hubs, cable glands, plugs
and sensor see 17.7 Tightening torque.
– For non-conduit installations, an approved cable gland
must be used (e.g. Hawke A501/421/A/¾" NPT or
equivalent)
Instructions for use
®
8xx0
®
|
Dräger Polytron
8000 Series