ELECTRICAL AND CONTROL SETTINGS
b. Installation of the ATW-RTU-04
In case of setting an installation with 2 circuits (circuit 1 and circuit 2) and the same demand ON/OFF is used for both of
them, remove the jumper between terminals 13 and 14 of the Terminal board 2 and connect the RF receiver as shown in the
following picture.
13
?
N O T E
•
If wireless intelligent thermostat is selected, optional ON/OFF thermostat has no effect.
•
Set the configuration in the user's control. See chapter
•
In case of setting an installation with 2 circuits (Circuit 1 and Circuit 2) and a different Demand ON/OFF is used for each of them, please refer to
"Input terminals (Optional input functions)"
ECO (input 2)
When enabled at Unit controller, both for circuit 1 and Circuit 2, also for heating and cooling, this input switches the unit to the
temperature configured.
The input can come from a push button, a thermostat or any other external device with that purpose.
Swimming pool (input 3)
When it is necessary to control the temperature of the swimming pool water, a connection between the heat pump and the
corresponding sensor must be done on terminals 16 and 17 at the Terminal board (input 4).
Solar (input 4)
This input comes from a solar panel sensor. The solar combination by input demand allows HSW to be heated by solar system when
there is enough solar energy available. The connection of this input signal has to be done between terminals 16 and 18 at TB2.
106
PMML0335A rev.1 - 04/2016
Jumper
14
"8 UNIT CONTROLLER"
section in this chapter.
13
Common
Line
Common
Line
16
Common
Line
13
14
Common
Line
Demand ON/OFF
Receiver input 2
Thermostat requirements:
•
•
for more information.
15
ECO
Input 2
16
17
SWP
IN
Input 3
18
Solar
IN
Input 4
Power supply: 230V AC
Contact voltage: 230V