Setting the main and sub remote controllers
1. Set one of the 2 connected remote controllers as the main remote controller.
2. On the other remote controller (sub-remote controller), switch the remote controller address connector on
the rear of the remote controller PCB from Main to Sub. When the connector has been switched, the remote
controller will function as the sub-remote controller.
NOTE
Cautions on group control
●
Group control within the same refrigerant tub-
ing system is recommended.
[Tubing system which is NOT recommended]
Tubing system 2
1
Remote controller
<Example 1> In this system, group control extending
over tubing systems becomes impossi-
ble to set, which means the indoor units
cannot operate.
DC_Inverter_Eng.indd 49
DC_Inverter_Eng.indd 49
To Service Technicians
To display the sensor temperature:
Press both
and
buttons on the
remote controller for more than 4 seconds
together.
Change the sensor address (CODE NO.)
with
/
(SET TEMP) buttons.
Select the UNIT NO. that you want to call
with
button.
Press the
button to finish service mode.
RCU.Main
RCU.CK
RCU.Sub
RCU
RCU.ADR
TMNL.
To avoid an electric shock hazard,
WA R N I N G
DO NOT touch any ter-
minal on the Printed Cir-
cuit Board with a metal rod, a
screwdriver edge or bare hand
when power
is supplied.
Tubing system 1
3
Indoor units
2
4
TIMER
TMNL.
To display the trouble history:
Press both
and
buttons on the
remote controller for more than 4 seconds
together.
Change the alarm message:
/
(SET TEMP) buttons
CODE NO.
(New) (Old)
Press the
button to finish service
mode.
Remote Controller (Main)
Changing method for room
temperature sensor (from Indoor
Remote Controller (Sub)
unit to RCU)
On the remote controller, press
1
+
+
at the same time for
more than 4 seconds.
Set CODE No.
with
/
2
(SET TEMP) button.
Set DATA from
to
3
with
/
(TIMER) button.
Press
4
Finally, Press
Fig. 6-6
49
GB
FR
Remote controller
DE
address connector
PT
GR
ES
2007/07/25 13:21:44
2007/07/25 13:21:44