EN
A
MOUNTING
Choose the optimal location: flat and large surface, open
the housing.
[1] Mount the KNX RS485 Motor Controller WM
[2] Mount the DIN rail version
1.
Vertical
2.
Horizontal
B
WIRING
[1] Finish wiring and connect KNX bus, keep minimum
distance
[2] Wiring diagram
[3] Check the correct running directions of the end product
UP: the end product goes up g
STOP: the end product stops g h
DOWN: the end product goes down h
CHARACTERISTICS
Supply voltage from KNX bus
Rated current consumption KNX
Terminals
Terminal KNX
Running time per output
Operating temperature
Relative humidity
Material of housing
Housing dimensions (w x h x d)
Weight
Degree of protection
Protection class
Conformity
CABLE
Connection to ...
RS485 bus
Modular Jack 8P4C (RJ45) Min.: 4 x 2 x 0.5 mm/24 AWG Required twisted pair shielded,
KNX bus
C
KNX voltage 21...32 V DC, SELV
As per KNX guidelines, <= 12.5 mA
RJ45
KNX bus terminal (black/red)
Max. 5 minutes
- 5 ° C to 50 ° C
Max. 85 %
PC-ABS
90 x 180 x 45 mm
175 g
IP 20
www.somfy.com/ce
Cable
2 x 0.8 mm/20 AWG
CONFIGURATION
[1] KNX Prog button
Wall mounted version
[2] Topology
1.
The stub must not exceed 10 m.
2.
The length of the RS485 bus must not exceed
200 m.
3.
Not more than 18 RS485 motors may be connect-
ed together.
RS485 motors can be connected via bridging
adapter. Different motor types can be used.
⚠ 2 RS485 Terminators are mandantory even if
only one motor is connected.
Twisted pair
impedance 100 Ω (-10 Ω/+30 Ω),
recommended CAT5-FTP,
following Somfy RS485 guidelines
Required, following
KNX topology guidelines
animeo KNX RS485 MOTOR CONTROLLER . REF. 5127869E -
Max. length
200 m/660 ft
-
8/20