Possible modes of operations
Function
Setting
Alarm Latch
YES: Enable alarm latching.
NO: Disable alarm latching (default).
1)
Automatic BIT
YES: Perform automatic & manual BIT
(default).
NO: Perform manual BIT only.
1)
Alarm BIT
YES: Successful manual BIT activates
the alarm relay for approximately
3 seconds (default).
NO: Successful manual BIT does not
activate the alarm relay.
2)
Auxiliary Relay
YES: Activate auxiliary relay at warning
level.
NO: Activate auxiliary relay at alarm
threshold (default).
(The auxiliary relay is latched only when the
programmable function Auxiliary Relay is
set to YES.)
1, 2)
Auxiliary BIT
YES: Successful manual BIT activates
the auxiliary relay for approximately
3 seconds (default).
NO: Successful manual BIT does not
activate the auxiliary relay
2)
EOL
YES: Auxiliary relay is used as End of
Line.
NO:
accordance with both auxiliary relay
and auxiliary BIT settings (default).
1)
not applicable for Dräger Flame 2570
2)
only available in wiring option 4 and 5
Auxiliary
relay
operates
Possible heated optics settings
The heated mode can be set to one of the following:
OFF: Detector window is not heated
ON: Detector window is continuously heated
Automatic (default):
You can define the start temperature below which the detector
window is heated. The default is 5 °C (41 °F).
The start temperature can be defined between 0 °C (32 °F) and
30 °C (86 °F).
The heating stops when the temperature is 15 °C (approx. 27 °F)
above the start temperature.
3.3.8
Powering up the flame detector
1. Power up the system.
2. Wait approximately 60 seconds for the flame detector to finish the
start-up procedure.
The startup procedure is as follows:
The status LED flashes yellow at 4 Hz.
A BIT is executed.
If the test was successful:
The status LED flashes green at 1 Hz.
The fault relay contacts close.
The 0-20 mA output is 4 mA.
in
en
Use
15