Troubleshooting

3.4

During use

3.4.1

General notes

After powering-up, the flame detector requires almost no attention to
function properly, but the following should be noted:
Do not expose the flame detector to radiation of any kind unless
required for testing purposes.
Do not expose the Dräger Flame 2100 to a UV radiation source
(for example: welding, sparks, electronic arc), as this will result in
a false alarm.
Do not open the detector housing while power is applied - there is
a risk of ignition of hazardous atmospheres.
Do not open the electronic compartment. This part should be kept
closed always and only opened in the factory. Opening the
electronic component side invalidates the warranty.
Only access the wiring compartment to wire or remove the
detector or access RS485 terminals for maintenance.
3.4.2

Manual reset

Note: Most detectors are used in the non-latching alarm mode. Only
perform a reset when the latching alarm option has been programmed.
Disconnect power (terminal number 1 or terminal number 2).
or
Initiate a manual BIT (Dräger Flame 2100/2350 only).
18
4
Troubleshooting
Problem
Cause
Status LED off
Flame detector not
Fault relay at N.O.
energized
0-20 mA output at
0 mA
Status LED flashes
Detector fault
yellow at 4 Hz
Low voltage
Fault relay at N.O.
Faulty
0-20 mA output at
detector
0 mA
Status LED flashes
BIT fault
yellow at 4 Hz
Faulty
Fault relay at N.O.
detector
0-20 mA output at
2 mA
Status LED lights
If no fire exists, the
constantly red
alarm is latched.
Corrective action
Check that the
correct power is
applied
to
the
flame detector.
Check
power
polarity.
Check wiring in
the
flame
detector.
Send the flame
detector to Dräger
for repairs.
Check the voltage
at
the
flame
flame
detector; verify at
least 24 V at the
detector terminal.
Send the flame
detector to Dräger
for repairs.
Clean
detector
flame
window.
Repower
the
flame detector.
Send the flame
detector to Dräger
for repairs.
Reset the flame
detector.