Obj Object name
44 Basic light-level threshold
This object is only visible if the "Threshold and 'ON' period can be read /
changed via bus" parameter is set to "Yes" in the "Basic Illumination" parameter
window.
The group address linked with this object can be used via bus for changing
the basic light-level threshold (in lux) at which basic illumination is activated if
not met and at which basic illumination is switched 'OFF' again if significantly
exceeded.
Any value received outside the permissible range of 10 to 100 lux is rejected.
This object can also be used for requesting the current threshold value at any
time, also after making a change by ETS or IR remote control.
Time factor for basic illumination
45
'ON' period
This object is only visible if the "Threshold and 'ON' period can be read /
changed via bus" parameter is set to "Yes" in the "Basic Illumination" parameter
window.
The group address linked with this object can be used for changing the 'ON'
period for basic illumination (in minutes) via bus. Basic illumination is switched
'OFF' after expiry of the 'ON' period.
Any value received outside the permissible range of 1 to 255 is rejected. This
object can also be used whenever necessary for requesting the current 'ON'
period for timed basic illumination, also after making a change by ETS or IR
remote control.
IR versions only:
Obj Object name
46 Light-level sensor input
This object is only visible if the "External light level" parameter is set to "YES"
in the "Light-Level Control" parameter window.
The group address linked with this object receives a light-level reading mea-
sured by a light-level sensor which is then used as a the setting for controlling
light level.
47 Sabotage protection
This object is only visible if the "Sabotage" parameter is set to "YES" in the

"General Settings" parameter window.

An ON or OFF telegram is sent cyclically to the group address linked to this
object while the sensor is not disconnected from the bus or if it is faulty.
HF 360 and Dual HF only:
Obj
Object name
46
Boost factor
This object is only visible if the "can be read / changed via bus" parameter is
set to "Yes" in the "HF settings" parameter window.
The group address linked with this object is used via bus for setting the HF
presence-detector boost factor. Any value received outside the permissible
range of 1 to 4 is rejected. This object can also be used for requesting the
current boost factor at any time, also after making a change by ETS or IR
remote control.
Values 1 to 4 have the following meaning:
1: very large movements are detected,
2: large movements are detected,
3: moderate movements are detected,
4: minor movements are detected.
47
Sensitivity
This object is only visible if the "can be read / changed via bus" parameter is
set to "Yes" in the "HF settings" parameter window.
The group address linked with this object is used via bus for setting the HF
presence-detector's "sensitivity". This object can also be used for requesting
the current sensitivity setting whenever necessary, also after making a change
by ETS or IR remote control.
How to calibrate presence detectors with constant-lighting control
Function
DP type
Flag
10...1000 Lux
9,004 (16 bits) CRWT
1...255
5,005 (8 bits)
CRWT
Function
DP type
Flag
10 to 1000 lux 9,004 (16 bits) CWT
ON/OFF
1,001 (1 bits)
CRT
Function
DP type
Flag
1...4
5,005 (8 bits)
CRWT
1 = high /
1,001 (1 bit)
CRWT
0 = low
Obj
Object name
48
Light-level sensor input
This object is only visible if the "External light level" parameter is set to "YES"
in the "Light-Level Control" parameter window.
The group address linked with this object receives a light-level reading mea-
sured by a light-level sensor which is then used as a the setting for control-
ling light level.
49
Light-level sensor input
This object is only visible if the "External light level" parameter is set to "YES"
in the "Light-Level Control" parameter window.
The group address linked with this object receives a light-level reading mea-
sured by a light-level sensor which is then used as a the setting for controlling
light level.
US 360, Single US, Dual US and Dual Tech only*:
Obj Object name
46
Ultrasonic boost
This object is only visible if the "can be read / changed via bus" parameter is
set to "Yes" in the "US settings" parameter window.
The group address linked with this object is used via bus for setting the US
presence-detector boost factor via the bus. Any value received outside the
permissible range of 0 to 255 is rejected.
48 Twilight sensor input
This object is only visible if the "External Light Level" parameter is set to "YES"
in the "Light-Level Control" parameter window.
The group address linked with this object receives a light-level reading meas-
ured by a light-level sensor which is then used as the setting for light-level
control.
49
Sabotage
This object is only visible if the "Sabotage" parameter is set to "YES" in the
"General Settings" parameter window.
An ON or OFF telegram is sent cyclically to the group address linked to this
object while the sensor is not disconnected from the bus or if it is faulty.
*Note: there is no parameter 47 (sensitivity) for US sensors

11. Parameters

Note: The parameter setting options corresponding to the factory set-
tings are shown in bold type.
11.1 "General Settings" parameter window
This parameter window is always available. It is used for setting the
detector operating mode as well as the chosen detector functions.
Parameter
Detector mode
Single detector: Only one presence detector is installed in the room.
Master: If required, additional detectors can be connected to the "master"
via bus as "slaves" to extend the presence detection zone. Only the master
controls light level and sends any presence and HVAC objects.
Slave: Slaves are used for extending the detection zone. They only deliver
presence information to the master.
Master in parallel mode: refer to page 1
Number of slaves
This parameter is only visible if the previous "Detector mode" parameter is
either set to "master" or "master in parallel mode" .
This parameter is used for setting the number of slaves connected. Depend-
ing on the number selected, the associated objects and parameters are add-
ed to the master.
- 9 -
Function
DP type
Flag
10 to 1000 lux 9,004 (16 bits) CWT
10 to 1000 lux 1,001 (1 bits)
CWT
Function
DP type
Flags
0...255
5,005 (8 bits)
CRWT
10 to 1000 lux 9,004 (16 bits) CWT
ON/OFF
1,001 (1 bit)
CRT
Settings
Single detector; Master; Slave;
Master in parallel mode
1; 2; 3; 4