After having carried out the various connections and having supplied voltage, all the LEDS
are switched off.
The motor opens and closes, but it has no strength and moves slowly.
The gate opens but does not close after the time set.
The gate does not close by activating the various START, RADIO and CLOSE buttons.
By activating the START, OPEN or CLOSE button the barrier does not move.
The slowing phase is not performed.
ACCESSORIES
For the connections and the technical data of the optional equipments follow the relevant handbooks.
PROBE
The probe detects the motor temperature to operate the heating system under low
temperature conditions, up to -30°C (connect to connector J6).
METALLIC MASS DETECTOR
to open with vehicles
1 channel - 230 Vac
1 channel - 12÷24 Vac/dc
2 channels - 12÷24 Vac/dc
FAULT
code ACG4666
code ACG9060
code ACG9063
code ACG9064
On the board there are resettable fuses which intervene in the event of a short circuit,
interrupting the output assigned to them.
In the event of troubleshooting, it is advisable to disconnect all the removable
connectors and insert them one at a time in order to more easily identify the cause
of the fault.
Check the integrity of fuse F1.
In case of interrupted fuse use only of adequate value
F1 = T 5A Fuse for motor protection
Check trimmers LOW SPEED OPEN and LOW SPEED CLOSE adjustment.
Make sure that the TCA trimmer is activated with LED DL11 ON.
B.I.O. contact always on / green led on => check the status of the clock connected to B.I.O.
input.
Photocells Auto-test failed => check the connections between the control panel and the
photocells.
Faulty safety edge contact. Faulty photocells contact => Fix or replace the faulty contact.
Photocells Auto-test failed => check the connections between the control panel and the
photocells.
START, OPEN or CLOSE command always active.
Check and replace any buttons or micro-switches of the selector switch.
Check LOW SPEED OPEN e LOW SPEED CLOSE trimmers adjustment.
NOVA - NOVA WIRELESS
PHOTOCELLS NOVA - range 25 m
PHOTOCELLS NOVA WIRELESS - range 25 m - 3 years batteries life
PAIR OF COLUMNS for NOVA
LOOP PRE-ASSEMBLED
6 m - perimeter 2 x 1 + 15 m of cable
10 m - perimeter 3 x 2 + 15 m of cable
40
SOLUTION
code ACG8046
code ACG8047
code ACG8039
code ACG9067
code ACG9068