How to install the electrical connection
Mounting the ARGUS in wall connection boxes:
Figure (:
1 In order to lead the connecting cable into the back of the device from
above, attach the four spacers supplied to the wall-mounting bracket.
Feeding in the connection cable from behind:
– push the rubber sleeves supplied A over the stripped connecting
cable.
Feeding in the connection cable from below:
– cut the rubber insert supplied B according to the cable thickness.
– Insert the rubber insert into the wall connection box
– Push through the connection cable
2 Mount the wall connection box using the screws supplied.
How to install the electrical connection
Note: Fuse the ARGUS using a 16 A automatic circuit-breaker.
|
Figure ):
1 Strip the connecting cable insulation by a length of 14 mm.
2 Insert the external conductor into terminal "L".
3 Insert the neutral conductor into terminal "N".
4 Insert the connected external conductor into terminal "
"Through-wiring" to other loads is permitted.
Note When switching inductive loads such as transformers, relays,
|
contactors or fluorescent lamps, spikes occur which could lead to
the load being switched on again ("maintained light effect").
Connect a capacitor (542895) parallel to the inductive load in order
to reduce these spikes.
Installation options (Figure )):
A ARGUS constantly connected to the mains:
ARGUS monitors its area constantly.
".
15
How to mount the ARGUS upper section
B ARGUS combined with two-way switch:
depending on the switch position, either maintained light or
automatic mode.
C ARGUS combined with break contact:
ARGUS is always ready for operation. By pressing the push-button
(the power is briefly disconnected for 2–3 seconds), the ARGUS is
switched on for the set time. Every further movement increases
the switching duration.
D ARGUS in parallel:
several ARGUS devices working together can switch a lamp group
if the maximum switching capacity of one device is not exceeded.
To achieve this, you must reduce the sensitivity of the devices. For
technical and functional reasons, we do not advise forming larger
device groups using more than four ARGUS devices.
E ARGUS combined with two-circuit switch:
depending on the switch position, either automatic mode or "OFF".
In position A, the luminaire is switched on by the ARGUS
(automatic) and in position B, it is switched on continuously
(manual).
F ARGUS parallel to the staircase timer:
either the ARGUS or the staircase timer switches the lights on for
a certain period.
How to mount the
ARGUS upper section
Figure =:
1 Place the ARGUS upper section onto the connection box and fasten
it using the two screws provided (A). The electrical connection from
the terminal box to the pins is established automatically when the
screws are tightened.
2 Position the cover plate at the markings on the side, and guide it
upwards (B).
16