Herunterladen Diese Seite drucken

Transport - Dimplex LA 18I-MU Montage- Und Gebrauchsanweisung

Vorschau ausblenden Andere Handbücher für LA 18I-MU:

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

LA 18I-MU
5

Transport

ATTENTION!
When transporting the heat pump, ensure that it is not tilted by more than
45° (in any direction).
A pallet should be used to transport the heat pump to its final in-
stallation location. The basic device can be transported with a lift
truck, hand truck or by means of 3/4" pipes fed through the holes
in the baseplate or frame.
The heat pump and the transport pallet are joined by four transit
bolts. These must be removed.
Before using the transport holes in the frame, it is necessary to
remove the two side panel assemblies. Each covering panel is
secured with two screws. After the screws are loosened, the pan-
els must be tilted and pulled out of the kickplate.
1.
1.
2.
3.
The top fan panel, which does not have to be removed for trans-
portation, can be hung out of the cover panel. Rehang the panel
by gently pushing it in an upwards direction.
NOTE
Be careful not to damage any components when inserting the pipes
through the frame.
All black dust caps must be snapped back into the transport
holes at the installation location.
After transportation, the transport fastening in the device is to be
removed from both sides of the base.
www.dimplex.de
ATTENTION!
Before commissioning, the transport fastening must be removed.
3.
3.
2.
1.
452168.66.09 · FD 9706
English
Remove/screw in
transport lock
EN-5

Werbung

loading