5.5. Outside temperature probe

The outside temperature probe, supplied with the heat pump, has to be installed for the heat pump to work properly. Follow the
instructions below to install it.
Install the outside probe in a well ventilated area, but protected from wind and rain.
Do not install the outside probe at a distance of less than 1 m from windows or doors to avoid the effect of possible
currents of warm air.
Use a shielded 2-pole cable to prevent interferences.
Description
Outside temperature probe

5.6. External storage systems

These can be used to control DHW storage, heating and cooling temperatures using temperature probes.
Description
DHW inter-accumulator
Heating buffer storage tank
Cooling buffer storage tank

5.7. External production equipment

These are used to control production equipment handling of the various services, such as bypass valves or circulatory pumps.
Description
Heating / cooling consumption
Active cooling production
Passive cooling production
Pool production
DHW production
DHW Recirculation
5.8. DG1 – SG4 Outlet Units
The heat pump can control a direct outlet unit (DG1) and three outlet units with mixture (SG2, SG3 and SG4). Unit activation can be
controlled according to heating or cooling demand. In addition, the units with mixture can measure the unit's outlet temperature
and generate a regulation signal for the 3-way modulating valve.
Description
DG1 direct unit
SG2 unit with mixture
SG3 unit with mixture
SG4 unit with mixture
Signal
Analogue input
Table 1.1. Outside temperature probe connection terminals.
Signal
Analogue input
Analogue input
Analogue input
Table 1.2. Connection terminals for outlet units.
Signal
Digital output
Digital output
Digital output
Digital output
Digital output
Digital output
Table 1.3. Auxiliary equipment connection terminals.
Signal
Digital output
Analogue input
Analogue output
Digital output
Analogue input
Analogue output
Digital output
Analogue input
Analogue output
Digital output
Table 1.4. Connection terminals for outlet units.
53
Installer manual ecoGEO
Type
NTC 10K 25ºC Probe
Type
NTC 10K 25ºC Probe
NTC 10K 25ºC Probe
NTC 10K 25ºC Probe
Type
Activation 230Vac / 2A maximum
Activation 230Vac / 2A maximum
Activation 230Vac / 1A maximum
Activation 230Vac / 2A maximum
Activation 230Vac / 2A maximum
Activation 230Vac / 2A maximum
Type
Activation 230Vac / 2A maximum
NTC 10K 25ºC Probe
Valve regulation 0 – 10Vdc
Activation 230Vac / 2A maximum
NTC 10K 25ºC Probe
Valve regulation 0 – 10Vdc
Activation 230Vac / 2A maximum
NTC 10K 25ºC Probe
Valve regulation 0 – 10Vdc
Activation 230Vac / 2A maximum
Connector
AI11
Connector
AI10
AI15
AI16
Connector
DO12
DO13
DO1
DO2
DO3
DO4
Connector
DO5
AI12
AO3
DO6
AI13
AO4
DO14
AI14
AO5
DO15