24 V supply
Terminal X11
SSP9400X11
Terminal data
Flexible
With wire end
ferrule
Stripping length / contact length: 10 mm
Digital inputs, digital outputs
Terminal X12
SSP9400X12
Terminal data
Flexible
With wire end
ferrule
Stripping length / contact length: 10 mm
EDK94PNE36 DE/EN/FR/ES/IT 5.0
Wiring of the standard device
Labelling
Description
GE
GND external supply
24E
24 V external supply through safely separated power supply unit
(SELV/PELV)
IEC 61131−2, 19.2 ... 28.8 V, residual ripple max. ±5 %
Current during operation: 450 mA
Starting current: 4 A for 100 ms
Conductor cross−section
2
[mm
]
0.2 ... 2.5
labelling
Description
GOI
GND digital out/in
DI1
External control of the brake chopper; its only purpose is to
synchronise the brake choppers if a second power supply module is
used.
DO1
without function
DO2
Brake chopper active: HIGH level
DO3
Short circuit of brake chopper,
active: LOW level (fail−safe)
DO4
Overtemperature of heatsink,
active: LOW level (fail−safe)
Conductor cross−section
2
[mm
]
0.2 ... 2.5
l
Tightening torque
[AWG]
[Nm]
24 ... 12
Spring terminal
Tightening torque
[AWG]
[Nm]
24 ... 12
Spring terminal
8
[lb−in]
Reset by switching of
24 V at X11.
[lb−in]
53