Return/supply air temperature
2
159
differential setpoint
Return/supply air temperature
2
160
proportional band
Setpoint for differential pressure
1
161
indicating air flow present
Setpoint for differential pressure
1
162
indicating filter fouling
Setpoint for differential pressure
1
163
indicating filter blocked
Warm-up at fan start-up (validation of
2
185
detection of T° and RH exceeded)
2
186
Application of control at fan start-up
Fault taken into account when
2
188
temperature or relative humidity
exceeded
2
190
Post-ventilation of electric heater
Delayed fan control after operation
2
191
request.
2
192
Duration of fan soft start incline
Rotation time delay
2
193
for refrigerating circuits
1
200
Temperature upper limit threshold
1
201
Temperature low limit threshold
1
202
Humidity upper limit threshold
1
203
Humidity low limit threshold
3
204
Test mode
2
215
Unit number on console
6.1.3 Reading parameters (sub-menu 3.3)
This third sub-menu gives access to all the values (temperatures, relative humidities, pressures, time delays, meters, input and
output states, etc.) managed by the CCU CONTROLLER.. Only the useful parameters are displayed. They cannot be modified
The meters can be reset to zero. To do this, place the cursor on the chosen meter and simultaneously press the Reset and 0 keys
for 5 to 6 seconds.
All these parameters are accessible from the "customer" access level.
RETURN/SUPPLY AIR TEMPERATURE CONTROL
5.0 to 20.0°C
1.0 to 10.0°C
CHECK THE FILTERS
The values correspond to the unit's maximum air flow.
If there is a variation in the fan speed, these values are reduced proportionally
10 to 80 Pa
60 to 500 Pa
100 to 550 Pa
5 to 180 min
10 to 180 s
1 to 5 min
1 to 300 min
0 to 480 s
0 to 500 s
0 to 240 h
CHECKING WHETHER TEMPERATURE THRESHOLDS ARE EXCEEDED
30 to 75°C if P07 = 0
(P103 + P104) to 75°C if P07 > 0
30 to 75°C if P08 = 0
5°C to (P106 - P107) if P08 > 0
CHECKING WHETHER HUMIDITY THRESHOLDS ARE EXCEEDED
40 to 100% RH if P09 = 0
(P109 + P110) to 100% RH if P09 > 0
10 to 40% RH if P10 = 0
10% RH to (P115 - 116) of P10 > 0
0: no
1: yes
MASTER/SLAVE BUS
1 to 32
EN - 16
TIME DELAY
TEST MODE
10.0°C
P2 = 16
2.0°C
P2 = 16
30 Pa
150 Pa
190 Pa
30 min
30 s
2 min
10 min
P08 = 2 or 3
0 s
30 s
P02 > 9
240 h
P17 = 3, 4 or 6
40°C
P07 or P08 > 0
10°C
P07 or P08 > 0
80% RH
P09 or P10 > 0
20% RH
P09 or P10 > 0
0
P17 > 0
1