Function settings (continued)
Night-purge setting 4)
No.33
Time span for memorizing
Set one of conditions for Night-purge start, time span for memorizing
the threshold of outdoor temperature.
For example;
If Lossnay unit operates everyday, please set "24 hrs (factory
setting)".
If Lossnay unit stops during weekend, please set "72 hrs" so that
Lossnay can start Night-purge in the Monday morning.
This function is N/A from Lossnay unit DIP-SW.
DIP-SW
PZ-61DR-E
Setting
check
SW No.
Setting
Function No. Setting Data
-
-
N/A
33
-
-
-
-
No.34
Input priority setting
Set to follow input to the main unit from air conditioner, fan speed
controller, etc.
This function is N/A from Lossnay unit DIP-SW.
DIP-SW
PZ-61DR-E
Setting
check
SW No.
Setting
Function No. Setting Data
-
-
N/A
34
-
-
No.36
Outdoor temperature display setting
Set to display outdoor temperature detected by Lossnay unit
thermistor or not.
This function is N/A from Lossnay unit DIP-SW.
DIP-SW
PZ-61DR-E
Setting
check
SW No.
Setting
Function No. Setting Data
-
-
N/A
36
-
-
No.37
Indoor temperature display setting
Set to display indoor temperature detected by Lossnay unit thermistor
or not.
This function is N/A from Lossnay unit DIP-SW.
DIP-SW
PZ-61DR-E
Setting
check
SW No.
Setting
Function No. Setting Data
-
-
N/A
37
-
-
Calculated supply air temperature display
No.38
setting
Set to display calculated supply air temperature or not.
This function is N/A from Lossnay unit DIP-SW.
DIP-SW
PZ-61DR-E
Setting
check
SW No.
Setting
Function No. Setting Data
-
-
N/A
38
-
-
Time span for memoriz-
Setting
ing
check
0
24 hrs
(Factory setting)
1
48 hrs
2
72 hrs
Setting
Input priority setting
check
0
Main unit input priority
(Factory setting)
1
Individual input priority
Setting
Outdoor temperature
check
display
0
N/A
(Factory setting)
Display on the screen of
1
PZ-61DR-E
Setting
Indoor temperature
check
display
0
N/A
(Factory setting)
Display on the screen of
1
PZ-61DR-E
Setting
Calculated supply
check
temperature display
0
N/A
(Factory setting)
Display on the screen of
1
PZ-61DR-E
Temperature exchange efficiency
No.39, 40
setting
Set the 10 digit of temperature exchange efficiency which is used to
calculate supply air temperature.
This function is N/A from Lossnay unit DIP-SW.
DIP-SW
PZ-61DR-E
Setting
check
SW No.
Setting
Function No. Setting Data
-
-
-
-
-
-
-
-
-
-
N/A
39
-
-
-
-
-
-
-
-
-
-
DIP-SW
PZ-61DR-E
Setting
check
SW No.
Setting
Function No. Setting Data
-
-
-
-
-
-
-
-
-
-
N/A
40
-
-
-
-
-
-
-
-
-
-
No.41
Outdoor temperature correction
Set the correction for the outdoor temperature displayed on the
PZ-61DR-E screen by function
No. 36
This function is N/A from Lossnay unit DIP-SW.
DIP-SW
PZ-61DR-E
Setting
check
SW No.
Setting
Function No. Setting Data
-
-
-
-
-
-
-
-
-
-
-
-
-
-
N/A
-
-
41
-
-
-
-
-
-
-
-
-
-
-
-
-
-
Setting
10 digit of temperature
check
exchange efficiency
0
0
1
1
2
2
3
3
4
4
5
5
6
6
7
7
(Factory setting)
8
8
9
9
Setting
1 digit of temperature
check
exchange efficiency
0
0
(Factory setting)
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
9
9
.
Setting
The correction to
check
thermistor detection
0
-7 ˚C
1
-6 ˚C
2
-5 ˚C
3
-4 ˚C
4
-3 ˚C
5
-2 ˚C
6
-1 ˚C
7
0 ˚C
(Factory setting)
8
+1 ˚C
9
+2 ˚C
10
+3 ˚C
11
+4 ˚C
12
+5 ˚C
13
+6 ˚C
14
+7 ˚C
Eng-17