Function settings (continued)
Filter maintenance and fan power up
No. 1
setting against filter choking
Set the schedule for filter cleaning based on the estimated
concentration of dust in the air.
When fan power up is available, exhaust and supply fans power up at
1,000 hrs and 2,000 hrs gradually .
If function
No. 55
or
No. 56
is already worked, fan power up function
may not available.
Estimated hour differs by actual operated fan speed.
DIP-SW
PZ-61DR-E
Setting
check
SW No.
Setting
Function No. Setting Data
-
-
-
-
SW5-5
1
OFF
(Factory setting)
ON
CAUTION
• When the setting for the cumulative operation time of the
Lossnay is exceeded, the filter cleaning icon will appear
on the indoor unit remote controller or the Lossnay remote
controller. After cleaning the filter, the filter cleaning icon
can be reset. Refer to the Instruction book for the remote
controller.
Lossnay core maintenance indicator
No. 2
setting
Set to enable Lossnay core maintenance display. Estimated hour
differs by actual operated fan speed.
This function is N/A from Lossnay unit DIP-SW.
DIP-SW
PZ-61DR-E
Setting
check
SW No.
Setting
Function No. Setting Data
-
-
N/A
2
-
-
Automatic recovery setting after power
No.5
interruption
Sets for automatic recovery following power interruption.
DIP-SW
PZ-61DR-E
Setting
check
SW No.
Setting
Function No. Setting Data
-
-
OFF
(Factory setting)
SW5-4
5
-
-
ON
No. 6
Indoor negative pressure setting
Exhaust fan speed becomes
bigger than supply fan speed.
Remote controller indicates fan
speed of exhaust fan.
DIP-SW
PZ-61DR-E
Setting
check
SW No.
Setting
Function No. Setting Data
-
-
OFF
(Factory setting)
SW2-4
6
ON
-
-
Setting
Filter maintenance
Fan power
check
indicator
UP
0
DIP-SW priority
(Factory setting)
Indicate at
1
N/A
estimated 3,000 hrs
2
N/A
N/A
Indicate at
3
Available
estimated 3,000 hrs
Setting
Lossnay core
check
maintenance indicator
0
N/A
(Factory setting)
1
Indicate at estimated 6,000 hrs
Setting
Automatic recovery
check
0
DIP-SW priority
(Factory setting)
1
Stop when the power is on
2
Start when the power is on
Lossnay returns to the
3
state before interruption
Supply fan
Fan speed
Exhaust
Display
fan
1 down 2 down
4
4
3
3
3
2
2
2
1
1
1
1
Setting
Down level of supply fan
check
speed
0
DIP-SW priority
(Factory setting)
1
N/A
Supply fan speed is 1
2
down to exhaust fan speed
Supply fan speed is 2
3
down to exhaust fan speed
No.7
Indoor positive pressure setting
Supply fan speed becomes bigger
than exhaust fan speed.
Remote controller indicates fan
speed of supply fan.
DIP-SW
Setting
check
SW No.
Setting
-
-
OFF
(Factory setting)
SW2-5
ON
-
-
Max. fan speed setting during the first 30
No.8
minutes
This sets the fan to run forcibly for 30 minutes when operation starts
to ventilate the indoor area. After 30 minutes, fan speed can be
changed.
Use this setting if the indoor air is contaminated at night when the
system is shut down and you desire to ventilate the indoor area
quickly when operation is started in the morning.
This function is N/A from Lossnay unit DIP-SW.
During this function is working,
selected fan speed is displayed.
DIP-SW
Setting
check
SW No.
Setting
-
-
N/A
-
-
No.9
Delay start setting for air conditioner starting
Delays Lossnay operation for 30 minutes when City Multi or Mr. Slim
starts operating or when a external device starts operating.
This function is available only when Lossnay is interlocked with air
conditioners. This function is N/A during Night-purge.
DIP-SW
Setting
check
SW No.
Setting
-
-
OFF
SW5-1
(Factory setting)
-
-
ON
Exhaust fan setting during air conditioner
No.13
defrosting
This function can be used under the condition Lossnay supply duct is
connected to Mr. Slim or City Multi indoor unit.
Sets the operation of the exhaust fan during defrosting of the air
conditioner (when supply fan stop).
2
1
To enable this function, it is necessary to set the DIP-SW of the
1
indoor unit also. Please refer to its manual.
1
DIP-SW
Setting
check
SW No.
Setting
-
-
SW5-3
ON
OFF
(Factory setting)
Fan speed
Supply
Display
fan
4
4
3
3
2
2
1
1
PZ-61DR-E
Setting
Down level of exhaust
check
fan speed
Function No. Setting Data
0
DIP-SW priority
(Factory setting)
1
N/A
7
Exhaust fan speed is 1
2
down to supply fan speed
Exhaust fan speed is 2
3
down to supply fan speed
is displayed at PZ-61DR-E and
PZ-61DR-E
Setting
Max. fan speed setting
check
during the first 30 minutes
Function No. Setting Data
0
N/A
(Factory setting)
8
1
Available
PZ-61DR-E
Setting
Lossnay delay start
check
Function No. Setting Data
0
DIP-SW priority
(Factory setting)
1
N/A
9
2
15 min
3
30 min
PZ-61DR-E
Setting
Exhaust fan operation during
check
air conditioner defrosting
Function No. Setting Data
0
DIP-SW priority
(Factory setting)
13
1
Stop
2
No change
Exhaust fan
1 down 2 down
3
2
2
1
1
1
1
1
Eng-15