European Union Directive Compliance
If this product has the CE mark, it is approved for installation within the
European Union and EEA region. It has been designed and tested to meet the
following directives.
EMC Directive
This product is tested to meet Council Directive 89/336/EEC Electromagnetic
Compatibility (EMC) and the following standards, in whole or in part:
EN 50081-1:1992 EMC – Generic Emission Standard, Part 1 – Residential,
Commercial, and Light Industry
EN 50082-2:1995 EMC – Generic Immunity Standard, Part 2 – Industrial
Environment
The product described is intended for use in an industrial, light industrial or
commercial environment.
Wiring and Safety Guidelines
Install the PanelView 1400 terminal using publication 70E, Electrical Safety
Requirements for Employee Workplaces. In addition to the NFPA general
guidelines, follow these recommendations:
Connect the PanelView terminal to its own branch circuit
The input power source should be protected by a fuse or circuit breaker rated
at no more than 15 amps.
Route incoming power to the PanelView 1400 terminal by a separate path
from the communications cable.
Where power and communication lines must cross, they should cross at right
angles. Communications lines can be installed in the same conduit as low
level DC I/O lines (less than 10 Volts).
Grounding minimizes noise from Electromagnetic Interference (EMI) and is a
safety measure in electrical installations. To avoid EMI, shield and ground
cables appropriately.
A source for grounding recommendations is the National Electrical Code
published by the National Fire Protection Association of Boston.
PanelView 1400 Terminals