ELECTRICAL WORK

WARNING
1. Using the specified wires, ensure that the wires are
connected, and fix wires securely so that the external
tension to the wires does not affect the connecting
part of the terminals.
Incomplete connection or fixation may cause a fire, etc.
2. Be sure to connect the earth wire. (grounding work)
Incomplete grounding may lead to electric shock.
Do not connect ground wires to gas pipes, water pipes,
lightning rods or ground wires for telephone wires.
3. The appliance shall be installed in accordance with
national wiring regulations.
Capacity shortages of the power circuit or an incomplete
installation may cause an electric shock or fire.
CAUTION
Wrong wiring may cause a burn-out of some electrical
parts.
Be sure to use the cord clamps attached to the product.
Do not damage or scratch the conductive core or inner
insulator of the power and inter-connecting wires when
peeling them.
Use the power and Inter-connecting wires with specified
thicknesses, specified types and protective devices
required.
Remove the panel, and you can see electric parts on the
front side.
A metal pipe can be installed through the hole for wiring.
If the hole size does not fit the wiring pipe to be used, drill
the hole again to an appropriate size.
Be sure to clamp the power wires and indoor/outdoor
connecting wires with a banding band along the
connecting pipe so that the wires do not touch the
compressor or discharge pipe.
(The compressor and the discharge pipe become hot.)
Furthermore, be sure to secure these wires with the pipe
valve fixing plate and cord clamps stored in the electric parts
box.
Wiring between Indoor Unit and Out-
door Unit
The dashed lines show on-site wiring.
(Main circuit)
Input power
220-240 V~,
50 Hz
Earth
Leakage
breaker
Connect the indoor/outdoor connecting wires to the
identical terminal numbers on the terminal block of each
unit.
Incorrect connection may cause a failure.
For the air conditioner, connect a power wire with the
following specifications.
Model RAV-
Power supply
Maximum running
current
Installation fuse rating
Power wire
Indoor/outdoor
connecting wires
16
Electric parts box
Panel
Pipe valve
fixing plate
Cord clamp
Pipe hole
(Indoor/outdoor
connecting wires)
L
1
1
N
2
2
Remote
3
3
controller
Indoor unit
Outdoor unit
SP110
SP140
220-240 V~, 50 Hz
22.8 A
25 A (all types can be used)
H07 RN-F or 60245 IEC 66
2
(2.5 mm
or more)
H07 RN-F or 60245 IEC 66
2
(1.5 mm
or more)