FUNCTIONS TO BE IMPLEMENTED LOCALLY

Night operation control
Low-noise operation is available during nighttime hours
by connecting a commercially available timer and
separately sold applicable control wire TCB-KBOS1E.
For more information, refer to the manuals of these parts.
The power saving function of the air conditioner reduces
the level of nighttime operating noise.
Sufficient capacity for low-noise operation cannot always
be provided, depending on external conditions, including
the outside air temperature.
Handling Existing Pipe
When using the existing pipe, carefully check for the
following:
Wall thickness (within the specified range)
Scratches and dents
Water, oil, dirt, or dust in the pipe
Flare looseness and leakage from welds
Deterioration of copper pipe and heat insulator
Cautions for using existing pipe
Do not reuse a flare nut to prevent gas leaks.
Replace it with the supplied flare nut and then process it
to a flare.
Blow nitrogen gas or use an appropriate means to keep
the inside of the pipe clean. If discolored oil or much
residue is discharged, wash the pipe.
Check welds, if any, on the pipe for gas leaks.
When the pipe corresponds to any of the following, do not
use it. Install a new pipe instead.
The pipe has been opened (disconnected from indoor
unit or outdoor unit) for a long period.
The pipe has been connected to an outdoor unit that
does not use refrigerant R22, R410A or R407C.
The existing pipe must have a wall thickness equal to or
larger than the following thicknesses.
Reference outside
diameter (mm)
Ø9.5
Ø15.9
Ø19.1
Do not use any pipe with a wall thickness less than these
thicknesses due to insufficient pressure capacity.
EN
Wall thickness (mm)
0.8
1.0
1.0
19
To use an existing Ø19.1 mm pipe, set bit 3 of SW802
(switch for existing pipe) on the P.C. board of the outdoor
unit to ON. In this case, the heating performance may be
reduced depending on the outside air temperature and
room temperature.
When shipped from factory
Recovering Refrigerant
Use refrigerant recovery switch SW801 on the P.C. board
of the outdoor unit to recover refrigerant when the indoor
or outdoor unit is moved.
Procedure
1. Turn on the power of the air conditioner.
2. Select the FAN mode for indoor unit operation with the
remote controller.
3. Set SW804 on the P.C. board of the outdoor unit to all
OFF, and then press SW801 for 1 second or more. The
air conditioner enters the forced cooling mode for up to
10 minutes.
Operate or handle the valve to recover refrigerant during
this time period.
4. Upon completion of refrigerant recovery, close the valve
and press SW801 for at least 1 second to stop operation.
5. Turn off the power.
Refrigerant
recovery switch
SW801
Optional
connector CN610
Special operation
select switch
SW804
Existing pipe
switch SW802
DANGER
Be careful of electric shock because the P.C. board has an
electrical current running through it.
SW802
When using existing pipe
P.C. board