IO-Link Smart Sensor profile Ed. 2 (BML SL1-ALZ1-UE/MZZ-_U1L-...) (continued)
7.2

Process data (PD)

The variants of the BML use the IO-Link interface to
cyclically output a measurement value and additional
status and switching point information.
Byte
5
4
3
Measured value
Tab. 7-2:
Process data
Measurement Value
The measurement value represents the position of the
head in μm and consists of a signed 32-bit value.
Scaling factor
The scaling factor indicates what factor needs to be
multiplied by the measurement value in order to keep the
value in the SI units.
The BML scaling factor is  –6 (0xFA):
Measurement value × 10
= Position [m]
−6
Status and SSC
Bit Name
Function
7
System Error
The BML no longer functions
(memory error, hardware defect).
6
Out of Range /
The BML does not detect an
No
head in the detection range.
Measurement
Data
5
Not used
4
Measurement
The head is within the set
Value Unsafe
measuring range, but the function
reserve is low. The threshold for
the signal can be set using the
parameter Low Signal Quality
Threshold (see Section 7.5.10).
(Only available for
BML SL1-ALZ1-UEZZ-_U1L-...)
3
SSC 4
Switching information for the
fourth switchpoint
2
SSC 3
Switching information for the third
switchpoint
1
SSC 2
Switching information for the
second switchpoint. In SIO mode
SSC2 is on output OUT2.
0
SSC 1
Switching information for the first
switchpoint. In SIO mode SSC 1
is on output OUT 1.
Tab. 7-3:
Status and SSCs
www.balluff.com
2
1
0
Status
Scaling
and
factor
SSCs
In case of error the data are indicated as invalid using the
PD Invalid Bit only if the device cannot provide any valid
data at all.
The IO-Link functionality PD Invalid Bit is
handled differently by different IO-Link masters
(see manual for the master used).
Measuring range
Status Bits
1)
Bit 4 0 0
Bit 6 1 1
see Tab. 7-3
1)
If this bit is set, the function reserve is low. The tape is damaged or too
2)
far away.
Fig. 7-1:
Areas and output
If the BML is still on the tape but outside the detection/
measuring range, the process data variable is replaced by
the following values:
Out of Range positive: 2'147'483'640 (0x7FFFFFF8)
Out of Range negative: –2'147'483'640 (0x80000008)
In case of error (if no tapes are detected) the process data
variable is replaced by the error value 2'147'483'644
(0x7FFFFFFC) (No Measurment Data).
Position
0/1
0 0
2)
0
1 1
english
25