Electrical Works; Wiring Connection - Toshiba RAS-10G2KVP-Serie Installationsanleitung

Split-type
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 47
The power supply can be selected to connect to indoor unit or outdoor unit. Choose proper way and connect the power supply and connecting cable by follow
the instruction as following.
Model
Power source
Maximum running current
Circuit breaker rating
Wire type :
Power supply cable
Connecting cable

Wiring Connection

Indoor unit
Wiring of the cable can be carried out without removing the main panel.
1. Remove the front panel.
Pull and lift up front panel until it stops, move arms on left and right side
to outward direction then pull toward you to remove front panel.
w Beware front panel fall down that may cause of injure or part damage.
Arm
2. Remove the terminal cover and cord clamp.
3. Insert the cable (according to the local cords) into the pipe hole on the
wall.
4. Take out the cable protrudes about 20 cm from the front.
5. Insert the cable fully into the terminal block and secure it tightly with
screws.
6. Tightening torque : 1.2 N·m (0.12 kgf·m)
7. Secure the cable with the cord clamp.
8. Fix the terminal cover and attach front panel to the indoor unit.
Front panel
Cable
How to attach the front panel
Carry out attaching in the reverse order to removal.
Keep front panel horizontally and put both arms into guides.
Make sure both arms are inserted completely.
If the gap between main panel and front panel isn't even, remove and attach
again.
01_1115751102-EN.indd 8
01_1115751102-EN.indd 8

ELECTRICAL WORKS

ELECTRICAL WORKS
RAS-10, 13, 16G2KVP Series
50Hz, 220-240V Single phase
60Hz, 220-230V Single phase
11A
15A
More than H07RN-F or 60245 IEC66 (1.5 mm
More than H07RN-F or 60245 IEC66 (1.5 mm
Arm
Terminals block
Main panel
Terminal cover
2
or more)
2
or more)
Main panel
CAUTION
• Be sure to refer to the wiring system diagram labeled inside the main
panel.
• Check local electrical cords and also any specifi c wiring instructions or
limitations.
Outdoor unit
1. Remove the valve cover from the outdoor unit.
2. Connect the cable to the terminals as identifi ed with their respective
matched numbers on the terminal block of indoor and outdoor unit.
3. When connecting the cable to the outdoor unit terminals, make a loop as
shown in the installation diagram of indoor and outdoor unit to prevent
water coming in the outdoor unit.
4. Insulate the unused cords (conductors) from any water coming in the
outdoor unit. Proceed them so that they do not touch any electrical or
metal parts.
8
Guide
Arm
Gap between main
panel and front panel
should be even.
Front panel
Terminals block
Valve cover
3/26/2557 BE 12:08 PM
3/26/2557 BE 12:08 PM