Herunterladen Inhalt Inhalt Diese Seite drucken

Device Setup - Elektro-Automatik PS 8040-170 3U Bedienungsanleitung

Ps 8000 3u serie
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Operating the device

8. Device setup

The device setup is intended to set parameters that are not con-
stantly altered. Three elementary settings are always available,
other settings only if a digital interface card is equipped.
The device setup can be accessed by pressing both pushbut-
tons of the rotary knobs simultaneously for >2s while the output
is switched off (see section „6.3. Further control elements") .
All interface specific settings remain unmodified when inserting a
different card. Thereby, the user don't has to setup the interface
card everytime the card type changes.
Following elementary settings are available:
Name: AutoPwrOn
Settings:
on, off
Meaning: „Auto Power On", if set to „on" it activates the resto-
ration of the last output state when the device was switched off
or when a blackout occured. This is intended to be used in case
the power supply is supposed to continue working as soon as
it is powered again. With „off" the output remains switched off.
Name:
AI range
Settings:
0-5, 0-10
Meaning: selects the control voltage range to use with the
analogue interface.
Name:
Contrast
Settings:
50...100
Adjusts the contrast of the LCD display.
For all interface cards this setting applies:
Name:
Device node
Settings:
1...30
Meaning: Selects the device's address (device node is taken
from the CAN terminology). When using the device on a bus sy-
stem (CAN or GPIB), every device must have a unique address!
Following settings only with CAN interface IF-C1 and device
firmware version up to 4.x:
Name:
Baud
Settings:
10k,25k,50k,100k,125k,250k,500k,1M
Meaning: Selects the CAN transmission baud rate.
Name:
RID
Settings:
0...31
Meaning: Selects the relocatable identifier segment (RID). Refer
to CAN terminology and external instruction manual for the IF-
C1 CAN interface card for further information.
Name:
Bus term
Settings:
yes, no
Meaning: activates/deactives the bus termination resistor of
the CAN interface card. This is required if the device is at the
end of the bus.
Following settings only with CAN interface IF-C1 and device
firmware version up to 4.x:
Name:
Baud
Settings:
10k,25k,50k,100k,125k,250k,500k,1M
Meaning: Selects the CAN transmission baud rate.
48
Date: 06-27-2011
Default:
on
Default:
0-10
Default:
70
Default:
1
Default:
100k
Default:
0
Default:
yes
Default:
100k
Name:
Base ID
Settings:
0x000...0x7FC
Meaning: Defines the base CAN ID of the device in steps of 4.
Every unit is assigned three CAN IDs, starting from the base
ID: base ID, base ID +1 and base ID + 2.
None if these IDs shall match the broadcast ID (see below)!
If this setting is selected for adjustment, you can switch the
value display between decimal and hexdecimal by pushing one
of the rotary knobs.
Also refer to the external instruction manual for the IF-C1 CAN
interface card for further information.
Name:
Broad ID
Settings:
0x000...0x7FF
Meaning: Defines the so-called broadcast CAN ID of the device.
This ID is seperate and shall not match any of the three normal
CAN IDs (see above). It is used to send messages to multiple
units on the bus at the same time, which use the same broad-
cast ID. This ID can only be used to send messages with set
values or status, but not query or read something from the units.
If this setting is selected for adjustment, you can switch the
value display between decimal and hexdecimal by pushing one
of the rotary knobs.
Also refer to the external instruction manual for the IF-C1 CAN
interface card for further information.
Name:
Bus term
Settings:
yes, no
Meaning: activates/deactives the bus termination resistor of
the CAN interface card. This is required if the device is at the
end of the bus.
Following settings only with RS232 interface IF-R1:
Name:
Baud
Settings:
9600, 19200, 38400, 57600
Meaning: Selects the serial transmission baudrate in baud.
Further parameters for the RS232 are not configurable, but
defined as follows:
Parity = odd
Stop bits = 1
Data bits = 8
and have to be set to the same configuration at the PC.
Following settings only with Profibus interface IF-PB1:
Name:
Profibus
Settings:
1-125
Meaning: Define the Profibus address of the device. This
address is used apart from the device node to implement and
access the unit on a field bus system.
© 2006, Elektro-Automatik GmbH & Co. KG
Irrtümer und Änderungen vorbehalten
EN
Default:
0x000
resp.
0...2044
Default:
0x7FF
resp.
0...2047
Default:
yes
Default:
57600
Default:
1
Instruction Manual
PS 8000 3U Series

Werbung

Kapitel

Inhaltsverzeichnis
loading

Inhaltsverzeichnis