English, Installer manual - ECS 40
General
This accessory is used when F1145/F1245 is installed in
houses with up to four different climate systems that re-
quire different flow line temperatures, for example, in
cases where the house has both a radiator system and
an under floor heating system.
The water flow in the climate systems together should
not exceed 1700 l/h.
Caution
Underfloor heating systems are normally
flow line temperature
°C.
Check the max temperature for your floor with
your floor supplier.
Component positions
AA5-S2
AA5-X4
AA5
FA1
Miniature circuit-breaker
X1
Terminal block, power supply
AA5
Accessory card
AA5-X2
Terminal block, sensors and external blocking
AA5-X4
Terminal block, communication
AA5-X9
Terminal block, circulation pump, mixing valve and auxiliary relay
AA5-S2
DIP switch
AA5-F1
Fine-wire fuse
max
set between 35 and 45
AA5-X2
AA5-F1
Contents
4 x
Cable ties
1 x
Circulation pump
1 x
Shunt motor
1 x
3-way valve
1 x
Kit for accessory card
2 x
Heating pipe paste
1 x
Aluminium tape
1 x
Insulation tape
2 x
Replacement gasket
2 x
Temperature sensor
1 x
Room sensor
FA1
AA5-X9
X1