Carrying out the functional test
1. Start drive:
1. Start inverter: X3/DI1 = HIGH.
a) If the inverter is equipped with an integrated safety system: X1/SIA = HIGH and X1/SIB = HIGH.
2. Activate preset frequency setpoint 1 (20 Hz) as speed setpoint: X3/DI4 = HIGH.
The drive rotates with 20 Hz.
3. Optional: activate the function for the reversal of rotation direction.
a) X3/DI3 = HIGH.
The drive rotates with 20 Hz in the opposite direction.
b) Deactivate the function for the reversal of rotation direction again: X3/DI3 = LOW.
Speed characteristic (example)
DI1
Drive follows frequency setpoint
AI1 [V]
10
0
DI4
Preset frequency setpoint 1 active
DI3
f [Hz]
set
60
50
20
0
5 s
-20
2. Stop drive:
1. Deactivate preset frequency setpoint 1 again: X3/DI4 = LOW.
2. Stop inverter again: X3/DI1 = LOW.
The functional test is completed.
The commissioning process of the drive solution is described in a separate commissioning instruc-
tion which can be found on the Internet in our download area:
http://www.lenze.com à Download
Initial switch-on / functional test with terminal control
Speed setpoint selection via X3/AI1 active
(In this example X3/AI1 is connected to GND)
5 s
Invert rotation active
Preset frequency
setpoint 1 (20 Hz)
Commissioning
5
t
t
t
t
t
29