Product designation

Manual conventional detector for use in interior areas, surface-mounted with
glass pane:
- FMC-300RW-GSGRD manual call point, red
- FMC-300RW-GSGBU manual call point, blue
- FMC-300RW-GSGYE manual call point, yellow.
Installation
For installation, see Fig. 1 - Fig. 8, page 4, 6.
Connection (see Fig. 3, page 4)
Position
Description
1
b1, a1 / b2, a2
2
E
3
-----------------
Functional test
1.
Unlock the maintenance flap with the test key and lift it up; see Fig. 9.1
and 9.2.
2.
Insert the test key and rotate it clockwise through 90°; see Fig. 9.3.
The LED is illuminated if an alarm is triggered.
To reset the manual call point to its starting position:
1.
Turn the test key counterclockwise through 90°; see Fig. 9.4.
The LED is extinguished.
2.
Return the maintenance flap to its starting position.

Technical specifications

Operating voltage
Current consumption
Alarm resistor
Permissible operating temperature -25 °C . . +70 °C
Protection class as per EN 60529
Dimensions
F01U045274 | A5 | 2008.03
Function
Incoming/outgoing
Shielding
End of line resistor (EOL)
20 V DC (8.5 V DC . . 30 V DC)
specified by the respective security
system
820 Ohm (+/- 10%, 8.5 to 30 VDC)
IP 54
87 x 87 x 56 mm