BASIC PARAMETERS

SETTING THE REQUIRED DAY TEMPERATURE
The required day temperature can be viewed, by choosing:
C O N T R O L L E R P A R A M E T E R S >
R E Q U I R E D D A Y T E M P E R A T U R E
SETTING THE REQUIRED NIGHT TEMPERATURE
The required night temperature can be viewed, by choosing:
C O N T R O L L E R P A R A M E T E R S >
R E Q U I R E D N I G H T T E M P E R A T U R E
FROST PROTECTION SETTING
When the heating is turned off or it is not necessary, the controller turns off the boiler. By
existing danger of freezing the boiler is automatically turned on, if the outdoor temperature
drops bellow the setted frost protection temperature.
Default setting is 2 °C and can be set in span between -20 and 10 °C.
Frost protection can be set by choosing:
C O N T R O L L E R P A R A M E T E R S >
F R O S T P R O T E C T I O N
Required room temperature is set on 6 °C by default and can be changed
with service parameter S1.11.
SUMMER/WINTER SWITCHOVER TEMPERATURE SETTING
The controller has a built-in function, which automatically turns the heating off, if the aver-
age 24h temperature is higher than the set summer/winter switchover temperature.
The heating is turned on again, when the average 24 h temperature drops bellow the set
switchover temperature. If the operation mode switch is in position »day temperature«,
than the described function is deactivated.
Default setting is OFF and can be set in span between 10 and 30 °C, OFF.
B A S I C P A R A M E T E R S >
B A S I C P A R A M E T E R S >
B A S I C P A R A M E T E R S >
29